Sanyo CHDXR09663, CHDX09663, CHDX07263 Simple setting items, Filter sign on times for each model

Models: CHDXR07263* CHDXR09663 CHDX07263 CHDX09663

1 142
Download 142 pages 31.63 Kb
Page 100
Image 100

2. Detailed Settings Function

W-2WAY ECO-i SYSTEM Remote Controller Functions

Simple setting items

Item code

Item

Description

 

 

 

01

Filter sign ON time setting

Changes the indoor unit filter lifetime when a high-performance filter or other

(filter lifetime)

optional product is installed.

 

 

 

 

02

Degree of filter fouling

Reduces the filter sign ON time to 1/2 of the standard time (setting at the time of

shipping) for cases when filter fouling is more severe than normal.

 

 

 

 

 

Filter sign ON times for each model

 

 

 

 

 

Filter sign ON time

 

 

 

 

 

 

 

 

 

 

Super

 

High

 

High

 

 

 

 

 

 

 

 

 

 

Standard

Long-life

 

performance

 

performance

Model

 

long-life

 

 

Model

 

 

 

 

 

65

 

90

data

 

 

 

 

 

 

 

 

 

Standard

High fouling

Standard

High fouling

Standard

High fouling

 

Standard

High fouling

 

Standard

High fouling

 

 

 

 

0000

1-Way Air Discharge

×

75

2500

1250

×

×

 

×

×

 

×

×

Semi-Concealed (A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0001

4-Way Air Discharge

×

×

2500

1250

5000

2500

 

2500

1250

 

×

×

(Mini)Semi-Concealed (X, XM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0005

(Slim)Concealed Duct (U, UM))

×

×

×

1250

5000

2500

 

2500

1250

 

5000

2500

0006

Concealed Duct

×

×

×

1250

×

×

 

2500

1250

 

5000

2500

High Static Pressure (D)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0007

Ceiling-Mounted (T)

×

×

2500

1250

×

×

 

2500

1250

 

×

×

0008

Wall-Mounted (K)

150

75

×

×

×

×

 

×

×

 

×

×

0010

Floor-Standing (F)

150

75

×

×

×

×

 

×

×

 

×

×

0011

Concealed-Floor Standing (FM)

150

75

×

×

×

×

 

×

×

 

×

×

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE

× indicates that there is no corresponding filter.

150 indicates the filter sign ON time that is set at shipment.

• High fouling: Set when is selected for the degree of filter fouling (item code ).

Pressure

differential

switch

×

×

×

×

×

×

×

×

Unit: hour

4

4 - 9

Page 100
Image 100
Sanyo CHDXR09663, CHDX09663, CHDX07263, CHDXR07263* service manual Simple setting items, Filter sign on times for each model