2. Detailed Settings Function

W-2WAY ECO-i SYSTEM Remote Controller Functions

Item code

Item

Description

 

 

 

 

 

Set when using a central control device.

03

Central control address

Used when setting the central control address manually from the

 

 

remote controller.

04

Operating mode priority change

Note (1)

 

 

 

NOTE

(1) Explanation of operation mode priority change

Enabled only in 2WAY MULTI heat-pump models.

<Function>

With indoor units that are installed in combination with an outdoor unit model where either heating or cooling operation can be selected, the operating mode of the indoor unit that starts first takes priority. The first indoor unit to operate can select any operating mode. When any mode other than fan mode is selected, then the operating modes that cannot be selected are not displayed on all remote controllers that are subsequently operated. “Operation change control in progress” is displayed, indicating that there are restrictions on the operating modes that can be selected.

Controlling the operating mode from a specific remote controller

-When there are multiple remote controllers in the same refrigerant system, it is possible to set one remote controller as the priority remote controller (the remote controller which is given priority for selecting the operating mode). (If 2 or more remote controllers are set as priority remote controllers, an alarm will occur at the remote controllers, and operation will not be possible.)

-When the priority remote controller is set to the operating mode for control, then all other remote controllers can select only the permitted operating mode, regardless of whether the priority remote controller is operating or

4stopped.

-When a controlled remote controller is operated, “Operation change control in progress” is displayed.

Set mode at priority remote controller

Modes that can be selected at other remote controllers

Cooling or dry

Cooling, dry, fan

Heating

Heating, fan

Fan

Whichever mode (heating/cooling) is selected first

NOTE

There are other methods to avoid control in which the mode selected first takes priority.

Methods of remotely controlling the operating mode

(1)Use the central functions of a central control device.

(2)Use a remote control relay PCB at the outdoor unit.

4 - 10

Page 101
Image 101
Sanyo CHDX09663 Explanation of operation mode priority change, Enabled only in 2WAY Multi heat-pump models, Function