4. W-2WAY ECO-i Alarm Codes

W-2WAY ECO-i SYSTEM Trouble Diagnosis

P03, P17 Alarm

 

 

 

 

 

Alarm code

P03, P17

 

 

 

 

 

 

 

Alarm meaning

Compressor 1 discharge temperature trouble; Compressor 2 discharge temperature trouble

 

 

Alarm conditions

Temperature is 222°F or higher and pre-trip stop has occurred.

 

 

 

The alarm occurs when pre-trip stop occurs more than once. However the pre-trip counter is

 

 

 

cleared if the compressor operates continuously for a specified length of time.

 

 

Probable cause

(1) Clogging of liquid valve capillaries

 

 

 

(2)

Insufficient amount of refrigerant (including trouble resulting from an insufficient initial charge

 

 

 

 

and from gas leakage)

 

 

 

(3)

Blocking of low-pressure parts caused by intrusion of foreign objects (moisture, scale, etc.)

 

 

 

(4)

Crossing (tubing or PCB connectors) with the other compressor thermistor

 

 

 

(5)

Expansion valve operation failure

 

 

 

(6)

Accumulation of refrigerant at stopped outdoor units

 

 

 

(7)

Compressor discharge sensor failure

 

 

 

(8)

PCB failure (A/D conversion failure)

 

 

 

(9)

Electrical noise

 

 

Check

(1) Clogging of capillaries

 

 

 

 

Trouble: Compressor discharge temperature does not decrease even when the liquid valve

 

 

 

 

 

is ON.

 

 

 

 

Check:

When the liquid valve is operating and the liquid valve is ON, check that the

 

 

 

 

 

secondary side of the liquid capillaries is cold.

 

 

 

(2)

Insufficient refrigerant

 

 

 

 

Trouble:

Liquid effectiveness is poor.

 

 

 

 

Check:

Check whether or not the superheating temperature is declining if the evaporator

 

 

 

 

 

mechanical valve is opened to 300 pulses or more (after checking for foreign object

 

 

 

 

 

intrusion).

 

 

 

(3)

Foreign object intrusion

 

 

 

 

Trouble:

Liquid valve effectiveness is poor.

 

 

 

 

Check:

Check that there is no difference in the condensation or frost conditions between

 

 

 

 

 

the strainer primary-side and secondary-side tubing.

 

 

 

(4)

Crossed thermistor

 

 

 

 

Trouble: The discharge temperature of the other compressor is high although only this

 

 

 

 

 

compressor is operating.

 

 

 

 

 

When the liquid valve turns ON, the discharge temperature of the other compressor

 

 

 

 

 

decreases.

 

 

 

(5)

Accumulation of refrigerant in stopped outdoor units

 

 

 

 

Trouble: • System is OK when all outdoor units are operating, however symptoms of

 

 

 

 

 

insufficient gas occur when a certain outdoor unit is stopped.

 

 

 

 

 

• Condensation or frost is visible up to the top of the accumulator of the stopped

 

 

 

 

 

outdoor unit.

 

 

 

 

 

• After an outdoor unit stops, there is the sound of refrigerant flowing into an outdoor

 

 

 

 

 

unit that was stopped for a long time.

 

 

 

 

 

• When an outdoor unit starts after being stopped for a long time, the start is

 

 

 

 

 

accompanied by much vibration.

 

5

 

 

Check: • Representative parts include the liquid capillaries (secondary side of capillaries will

 

 

 

 

be cool during cooling operation), mechanical valve, mechanical valve bypass check

 

 

 

 

 

valve (sound of refrigerant flow can be heard, and stops when the liquid valve is

 

 

 

 

 

closed), hot gas defrost valve (if valve secondary side remains hot even after much

 

 

 

 

 

time has passed, be careful not to mistake transmitted heat for a valve failure).

 

 

 

 

 

• Ice is growing on the lower parts of some outdoor unit heat exchangers but not on

 

 

 

 

 

others.

 

 

 

 

 

Because this trouble may occur even in outdoor units with a high operating rate

 

 

 

 

 

under conditions of insufficient gas, caution is needed.

 

 

 

(6)

Sensor failure

 

 

 

 

Check: • This alarm is likely to occur when wiring is partially cut. (It is difficult to identify, even

 

 

 

 

 

when continuity is checked.) The detected discharge temperature is high.

 

 

 

 

 

• Although such conditions rarely occur, a P02 alarm is likely if the detected discharge

 

 

 

 

 

temperature is low.

 

 

 

 

 

• Replace the sensor with another discharge sensor and compare the temperature

 

 

 

 

 

conditions.

 

 

 

(7)

If the cause is still unknown after checking the above, then it is possible that electrical noise

 

 

 

 

is the cause of the trouble.

 

 

Correction

(1) Replace the sensor.

 

 

 

(2)

Replace the outdoor unit PCB.

 

 

 

(3)

Correct the problem locations.

 

 

Example

All of the probable causes

 

 

Notes

Operates continuously for a set length of time.

 

 

 

Indicates 2.5 minutes or longer for an inverter unit and 30 seconds or longer for a constant-

 

 

 

speed compressor.

 

 

5 - 23

Page 132
Image 132
Sanyo CHDXR09663, CHDX09663, CHDX07263, CHDXR07263* service manual P03, P17 Alarm Alarm code