4. W-2WAY ECO-i Alarm Codes
P03, P17 Alarm |
|
|
|
|
|
Alarm code | P03, P17 |
|
|
| |
|
|
|
| ||
Alarm meaning | Compressor 1 discharge temperature trouble; Compressor 2 discharge temperature trouble |
|
| ||
Alarm conditions | Temperature is 222°F or higher and |
|
| ||
| The alarm occurs when |
|
| ||
| cleared if the compressor operates continuously for a specified length of time. |
|
| ||
Probable cause | (1) Clogging of liquid valve capillaries |
|
| ||
| (2) | Insufficient amount of refrigerant (including trouble resulting from an insufficient initial charge |
|
| |
|
| and from gas leakage) |
|
| |
| (3) | Blocking of |
|
| |
| (4) | Crossing (tubing or PCB connectors) with the other compressor thermistor |
|
| |
| (5) | Expansion valve operation failure |
|
| |
| (6) | Accumulation of refrigerant at stopped outdoor units |
|
| |
| (7) | Compressor discharge sensor failure |
|
| |
| (8) | PCB failure (A/D conversion failure) |
|
| |
| (9) | Electrical noise |
|
| |
Check | (1) Clogging of capillaries |
|
| ||
|
| Trouble: Compressor discharge temperature does not decrease even when the liquid valve |
|
| |
|
|
| is ON. |
|
|
|
| Check: | When the liquid valve is operating and the liquid valve is ON, check that the |
|
|
|
|
| secondary side of the liquid capillaries is cold. |
|
|
| (2) | Insufficient refrigerant |
|
| |
|
| Trouble: | Liquid effectiveness is poor. |
|
|
|
| Check: | Check whether or not the superheating temperature is declining if the evaporator |
|
|
|
|
| mechanical valve is opened to 300 pulses or more (after checking for foreign object |
|
|
|
|
| intrusion). |
|
|
| (3) | Foreign object intrusion |
|
| |
|
| Trouble: | Liquid valve effectiveness is poor. |
|
|
|
| Check: | Check that there is no difference in the condensation or frost conditions between |
|
|
|
|
| the strainer |
|
|
| (4) | Crossed thermistor |
|
| |
|
| Trouble: The discharge temperature of the other compressor is high although only this |
|
| |
|
|
| compressor is operating. |
|
|
|
|
| When the liquid valve turns ON, the discharge temperature of the other compressor |
|
|
|
|
| decreases. |
|
|
| (5) | Accumulation of refrigerant in stopped outdoor units |
|
| |
|
| Trouble: • System is OK when all outdoor units are operating, however symptoms of |
|
| |
|
|
| insufficient gas occur when a certain outdoor unit is stopped. |
|
|
|
|
| • Condensation or frost is visible up to the top of the accumulator of the stopped |
|
|
|
|
| outdoor unit. |
|
|
|
|
| • After an outdoor unit stops, there is the sound of refrigerant flowing into an outdoor |
|
|
|
|
| unit that was stopped for a long time. |
|
|
|
|
| • When an outdoor unit starts after being stopped for a long time, the start is |
|
|
|
|
| accompanied by much vibration. |
| 5 |
|
| Check: • Representative parts include the liquid capillaries (secondary side of capillaries will |
| ||
|
|
| be cool during cooling operation), mechanical valve, mechanical valve bypass check |
|
|
|
|
| valve (sound of refrigerant flow can be heard, and stops when the liquid valve is |
|
|
|
|
| closed), hot gas defrost valve (if valve secondary side remains hot even after much |
|
|
|
|
| time has passed, be careful not to mistake transmitted heat for a valve failure). |
|
|
|
|
| • Ice is growing on the lower parts of some outdoor unit heat exchangers but not on |
|
|
|
|
| others. |
|
|
|
|
| Because this trouble may occur even in outdoor units with a high operating rate |
|
|
|
|
| under conditions of insufficient gas, caution is needed. |
|
|
| (6) | Sensor failure |
|
| |
|
| Check: • This alarm is likely to occur when wiring is partially cut. (It is difficult to identify, even |
|
| |
|
|
| when continuity is checked.) The detected discharge temperature is high. |
|
|
|
|
| • Although such conditions rarely occur, a P02 alarm is likely if the detected discharge |
|
|
|
|
| temperature is low. |
|
|
|
|
| • Replace the sensor with another discharge sensor and compare the temperature |
|
|
|
|
| conditions. |
|
|
| (7) | If the cause is still unknown after checking the above, then it is possible that electrical noise |
|
| |
|
| is the cause of the trouble. |
|
| |
Correction | (1) Replace the sensor. |
|
| ||
| (2) | Replace the outdoor unit PCB. |
|
| |
| (3) | Correct the problem locations. |
|
| |
Example | All of the probable causes |
|
| ||
Notes | Operates continuously for a set length of time. |
|
| ||
| Indicates 2.5 minutes or longer for an inverter unit and 30 seconds or longer for a constant- |
|
| ||
| speed compressor. |
|
|
5 - 23