6. Operation of Solenoid Valves

W-2WAY ECO-i SYSTEM Control Functions

6-3. Recovery Valve (ORVR)

This valve recovers refrigerant oil from the balance tube to the compressor.

(1)When unit is stopped This valve is always OFF.

(2)When unit is operating

(A)This valve turns ON when separator oil self-recovery control is in progress.

1 (B) This valve is ON when unit refrigerant oil recovery control is in progress (oil-receiving unit).

(C)This valve is ON when control the system in case of insufficient refrigerant gas.

(D)This valve turns ON for 60 seconds after a constant-speed compressor starts.

(E)This valve turns ON for 120 seconds after defrost control ends.

(F)This valve turns ON for 10 seconds after the outdoor unit stops.

(G)This valve remains OFF at all times other than (A) through (F) above.

6-4. Bypass Valve (BPV)

This valve flushes the oil from the balance tubes. In addition, it is used for recovering refrigerant from stopped out- door units during cooling operation.

(1)When unit is stopped This valve is always OFF.

(2)When unit is operating

This valve is ON at the oil-supply outdoor unit when unit refrigerant oil recovery control is in progress.

* This valve repeatedly turns ON/OFF at regular intervals during unit refrigerant oil recovery control. (It is not constantly ON.)