4. W-2WAY ECO-i Alarm Codes

W-2WAY ECO-i SYSTEM Trouble Diagnosis

Check

(3)

Leakage from the discharge tube check valve

 

 

Trouble: Although the other compressor is operating and this compressor is stopped, the

 

 

 

discharge temperature of this compressor rises together with the temperature of the

 

 

 

other compressor.

 

 

(4) The ambient temperature around the outdoor unit when it is stopped is 109°F or higher.

 

 

(5)

If the cause is still unknown after checking the above, then it is possible that electrical noise is

 

 

 

the cause of the trouble. It is necessary to provide a line filter or carry out other noise

 

 

 

countermeasures.

 

Correction

(1)

Replace the sensor.

 

 

(2)

Replace the outdoor unit PCB.

 

 

(3)

Carry out noise countermeasures.

 

 

(4)

Repair the refrigerant tubing.

 

 

(5)

Adjust the amount of refrigerant.

 

 

(6)

Correct the trouble.

 

Example

(1)

Sensor wiring is partially cut.

 

Notes

This alarm does not indicate that the sensor is disconnected.

 

 

In order to prevent overheating during operation, the outdoor units in this system will not allow a

 

 

compressor to start if the discharge temperature does not decrease while the compressor is

 

 

stopped. If a sensor malfunction results in continuous detection of a high discharge temperature,

 

 

then the compressor may stop for no apparent reason. The purpose of this alarm is to facilitate

 

 

identification of the problem in this case.

 

F06, F23 Alarm

 

 

 

 

 

 

 

Alarm code

F06, F23

 

 

 

 

Alarm meaning

Gas temperature sensor trouble at outdoor heat exchanger 1; Gas temperature sensor trouble at

 

 

outdoor heat exchanger 2

 

Alarm conditions

(1)

A/D step is 10 steps or less (short circuit).

 

 

(2)

A/D step is 1014 steps or more (open circuit).

 

Probable cause

(1)

Sensor malfunction (including connector)

 

 

(2)

PCB malfunction

 

Check

(1)

Measure the sensor resistance. Check that the sensor is operating normally.

 

 

(2)

Use a remote controller monitor or PC monitor to check the temperature that is recognized by

 

 

 

the microcomputer.

 

Correction

 

 

 

Example

 

 

 

Notes

 

 

5

F07, F24 Alarm

 

 

 

 

 

 

 

 

 

 

Alarm code

F07, F24

 

 

 

 

 

 

Alarm meaning

Liquid temperature sensor trouble at outdoor heat exchanger 1; Liquid temperature sensor trouble

 

 

at outdoor heat exchanger 2

 

Alarm conditions

(1)

A/D step is 10 steps or less (short circuit).

 

 

(2)

A/D step is 1014 steps or more (open circuit).

 

Probable cause

(1)

Sensor malfunction (including connector)

 

 

(2)

PCB malfunction

 

Check

(1)

Measure the sensor resistance. Check that the sensor is operating normally.

 

 

(2)

Use a remote controller monitor or PC monitor to check the temperature that is recognized by

 

 

 

the microcomputer.

 

Correction

 

 

 

Example

 

 

 

Notes

 

 

 

5 - 13

Page 122
Image 122
Sanyo CHDX07263, CHDXR09663, CHDX09663, CHDXR07263* service manual F06, F23 Alarm Alarm code, F07, F24 Alarm Alarm code