2. Detailed Settings Function

W-2WAY ECO-i SYSTEM Remote Controller Functions

 

Item code

Item

Description

 

 

 

 

 

10

Unit type

Set when the indoor unit EEPROM memory is replaced during servicing.

 

 

 

 

11

Indoor unit capacity

 

 

 

 

 

 

 

12

System (outdoor unit)

 

 

address

These are not set at the time of shipping from the factory.

 

 

 

13

Indoor unit address

These must be set after installation if automatic address setting is not

 

performed.

 

 

 

 

14

Group address

 

 

 

 

 

 

 

 

Cooling intake temperature

Shifts the intake temperature during cooling and dry operation.

 

17

(Enabled only when the body thermostat is used.)

 

shift

 

 

Increase this value when it is difficult to turn the thermostat ON.

 

 

 

 

 

 

 

 

18

Automatic stop time after

The time at which an indoor unit is automatically stopped after operation starts

 

operation start

can be set in increments of 5 minutes.

 

 

 

 

 

 

 

 

 

Use this setting to change the time for forced operation at installation or

 

1b

Forced thermostat ON time

servicing from 5 minutes to 4 minutes.

 

 

 

(Enabled only with PAC-i models.)

 

 

 

 

 

1C

Cooling discharge

Shifts the set value for models which perform discharge temperature control.

 

temperature shift

 

 

 

 

 

(Discharge temperature control models: Floor discharge, wall built-in, direct

 

 

Heating discharge

 

1d

expansion coil outdoor air treatment, high-fresh)

 

temperature shift

 

 

 

 

 

 

 

 

 

 

 

“Auto heat/cool” selects the operating mode automatically based on the

 

 

Temperature shift for

difference between the room temperature and the temperature set on the

 

1E

cooling/heating change in

remote controller. This setting establishes a shift temperature for the heating/

 

 

“auto heat/cool” mode

cooling temperature setting relative to the remote controller temperature

4

 

 

setting.

 

 

 

 

 

 

Cooling temperature setting

Remote controller temperature setting

Shift temperature

(+)

Shift temperature

(–)

Heating temperature setting

4 - 12

Page 103
Image 103
Sanyo CHDXR07263*, CHDXR09663, CHDX09663, CHDX07263 service manual Detailed Settings Function