12. Indoor Unit Refrigerant Oil Self Recovery Control

W-2WAY ECO-i SYSTEM Control Functions

This control is carried out regularly in cooling mode only.

(1)During stopped, fan or thermostat OFF condition, indoor unit expansion valve is opened regularly for 1 to 2 min- utes regularly (at an interval of once every 2 hours.)

(2)During the thermostat ON, the indoor unit electronic thermostatic expansion valve is opened about 10 pulses from the current status.