W-2WAY ECO-i SYSTEM

2. Detailed Settings Function

Remote Controller Functions

 

 

 

 

 

Item code

Item

 

Setting data

 

No.

Description

 

 

 

 

 

 

0000

No forced operation

 

 

Automatic drain pump

0001

Forced operation for 1 minute

 

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

0060

Continuous operation

 

 

Ventilation fan operation

0000

None

 

 

0001

Ventilation fan operated by remote controller.

 

 

 

 

 

Wired remote controller

0000

Not used. (Body sensor is used.)

 

 

sensor

0001

Remote control sensor is used.

 

 

“Operation change

0000

Normal (displayed)

 

 

control in progress”

 

 

 

 

0001

Not displayed

 

 

display

 

 

OFF reminder function

0000

None

 

 

for when weekly timer is

 

 

 

 

0001

Only stop time setting is enabled.

 

 

used

 

 

Discharge temperature

0000

Discharge temperature control OFF

 

 

 

 

 

 

control

0001

Discharge temperature control ON

 

 

 

 

 

 

 

 

 

 

Heat exchanger

0013

Control temperature 55°F

 

 

temperature for cold air

0014

Control temperature 57°F

 

 

discharge

 

 

 

 

(Heat exchanger control

 

 

 

 

point for control to

0025

Control temperature 77°F

 

 

prevent cold air)

0026

Control temperature 78°F

 

 

Fan output switching

0000

Output linked with fan. (ON when indoor unit fan is operating.)

 

0001

Fan mode operation output

 

 

 

 

 

 

0000

No delayed start

 

 

 

0001

1 sec. delayed start

 

 

Drain pump delayed

0002

2 sec. delayed start

 

 

 

 

 

 

start time

 

 

 

 

 

0058

58 sec. delayed start

 

 

 

0059

59 sec. delayed start

 

 

 

0060

60 sec. delayed start

 

 

 

0000

Humidifier output OFF. Drain pump stopped.

 

 

 

0001

Humidifier output ON. Drain pump operates.

 

 

Humidifier setting

0002

Humidifier output ON. Drain pump operates for 1 minute when total humidifier

 

 

operating time reaches 60 minutes.

 

 

 

 

 

 

 

0003

Humidifier output ON. Drain pump stopped.

 

 

Flap operation mode

0000

Standard setting

 

 

0001

Draft reduction mode (Flap lower-limit position is shifted upwards.)

 

 

 

 

0000

Smudging reduction mode (Flap swing upper-limit position is shifted downwards.)

 

Flap swing mode

0001

Normal mode

 

 

 

0002

Draft reduction mode (Flap swing lower-limit position is upwards.)

4

4 - 7

Page 98
Image 98