6. Mode Settings

W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller

NSetting mode 1 <Operating procedure>

ŒPress and hold the (CHECK) button and

(VENTILATION) button simultaneously for 4 seconds or longer.

Press the temperature setting and buttons to change the item code. The item codes

and setting data are shown in the table of “List of Item Codes” on the next page.

ŽPress the timer time and buttons to change the setting data.

To confirm the changed setting data, press the

button.

(At this time, all displays stop blinking and remain lit.)

During this mode, “ ” is displayed, blinking.

The outdoor unit address display section displays “ALL,” the item code and number (DN value in the

3table), and the setting data (8 digits).

(The setting data is displayed in 8 digits. The display changes between the first 4 digits (Fig. A ) and the last 4 digits (Fig. B ).

When the first 4 digits are displayed, the top dot of the colon is illuminated.)

To exit the setting mode, press the (CHECK) button.

5

5

ADisplay of first 4 digits

2

13

BDisplay of last 4 digits

2

13

 

 

 

 

A and B are displayed alternately.

 

 

 

 

(Example shows display of 0000 0001.)

 

 

 

 

 

DN

Parameter

 

 

Description

 

 

 

 

 

 

0

= Sensor input not present. Control is performed.

 

Snowfall sensor usage

1

= Sensor input present. Control is performed.

 

2

= Sensor input not present. Control is not performed.

 

 

 

 

3

= Sensor input present. Control is not performed.

 

Outdoor unit fan Quiet

0

= Disabled

1 = Quiet mode 1

 

2

= Quiet mode 2

3 = Quiet mode 3

 

mode

 

4

= Quiet mode 4

 

 

 

 

 

 

0

= None

 

 

Energy saving mode

1

= Discharge temp. control only (Mode 3)

 

2

= Demand only (Mode 2)

 

 

 

 

 

 

3

= Discharge temp. control + Demand (Mode 1)

 

Energy saving operation

0 = Independent

 

 

plug

1 = All indoor units linked

 

 

Demand 1 current

0

= 0% 1 = 40 … 4 = 70 7 = 100 8 = 120

 

9

= 140 10 = 160 11 = 200 12 = –1 (no limit)

 

 

 

Demand 2 current

0

= 0% 1 = 40 … 4 = 70 7 = 100 8 = 120

 

9

= 140 10 = 160 11 = 200 12 = –1 (no limit)

 

 

 

 

 

3 - 12

 