4. W-2WAY ECO-i Alarm Codes

W-2WAY ECO-i SYSTEM Trouble Diagnosis

F16 Alarm

Alarm code

F16

 

 

Alarm meaning

High-pressure sensor trouble (abnormal rise in high pressure) (In some cases this may not be

 

the result of a high-pressure sensor malfunction.)

Alarm conditions

High-pressure SW activated although the detected pressure was lower (439.4 psi or below)

 

than the high-pressure SW activation pressure: Undershift

High-pressure SW failed to activate although the detected pressure was higher (497.5 psi or above) than the high-pressure SW activation pressure: Overshift

The saturation temperature at the detected pressure is 10°F or more below the highest indoor- unit E1 temperature continuously for 30 minutes.

High-pressure sensor disconnected or open circuit.

Probable cause

(1)

High-pressure sensor malfunction

 

(2)

Failure to connect the connector to the outdoor unit PCB

 

(3)

Failure to open the service valve

 

(4)

Clogged tubing

 

(5) Valve leakage

 

(6)

Over-charging

 

(7)

Outdoor unit PCB failure

 

(8)

Electrical noise

Check

(1)

High-pressure sensor failure

 

 

• Check the sensor resistance value. (Use a tester and measure the resistance between

 

 

sensor No. 1 and No. 3)

 

 

Resistance of less than 10kΩ indicates a short circuit or other trouble.

 

 

Resistance of 10kΩ - 200kΩ is normal. Resistance of more than 200kΩ indicates

 

 

an open circuit or other trouble.

 

 

• Connect a gauge to the high-pressure outlet and check for changes in the value

 

 

dispalyed by the monitoring software, and for large deviation of the gauge pressure.

 

 

• During heating, check whether the temperature is lower than the highest indoor-unit E1

 

 

temperature.

 

 

* The pressure detected by the high-pressure sensor is the highest pressure in the system.

 

 

Therefore during heating the converted saturation temperature will never be lower than

 

 

any indoor-unit E1 temperature. During cooling this temperature will never be lower

 

 

than the outdoor unit liquid temperature.

 

(2)

Failure to open the service valve, clogged tubing, valve leakage, over-charging.

 

 

In all of these cases an alarm occurs when there are rapid pressure fluctuations and tracking

 

 

of the detected pressure is poor.

 

 

• Check the open/closed status of the valve.

 

 

• Check for clogging of the tubing.

 

 

To check for clogging, disconnect the high-pressure sensor from the PCB and check

 

 

whether the high-pressure SW activates.

 

 

• Check for valve leakage and over-charging

 

 

When valve leakage or over-charging occurs, refrigerant is likely to accumulate in the

 

 

outdoor units or indoor units, resulting in a sudden rise in pressure at start that occurs

 

 

before the refrigerant in the heat exchanger is discharged.

 

 

* The representative valves to check are the liquid valves and mechanical valves.

 

(3)

Outdoor unit PCB failure

 

 

• The check items are the same as for a high-pressure sensor malfunction.

 

 

A normal PCB is needed to determine whether the problem is a PCB failure or a pressure

 

 

sensor malfunction. If an abnormality was found at the check items for a high-pressure

 

 

sensor malfunction, first try replacing the PCB and check again.

 

 

Trouble is corrected: Outdoor unit PCB failure

 

 

Trouble is not corrected: High-pressure sensor malfunction

 

 

Continued

5

5 - 15

Page 124
Image 124
Sanyo CHDXR09663, CHDX09663, CHDX07263, CHDXR07263* service manual F16 Alarm Alarm code