17. Service Maintenance Functions

W-2WAY ECO-i SYSTEM Control Functions

The outdoor unit EEPROM settings can be used for the following functions.

17-1. Outdoor Unit Noise Countermeasure: EEPROM 05 (set at each outdoor unit)

This unit includes 3 types of Quiet modes. (However, when they are engaged, operation is in Quiet mode 24 hours a day.) Selecting a Quiet mode results in operation that gives priority to reducing noise. Because these modes involve restrictions on outdoor unit fan modes and the operation frequency, the capacity will be somewhat reduced.

1

Setting

Max. fan mode

Effect

Amount of capacity reduction

 

 

 

 

0

14

Normal operation (setting at time of

0

 

 

factory shipment)

 

 

 

 

 

 

 

 

 

 

1

12

Noise reduced by approx. 1 – 2 dB from

Approx. 0.5 hp

 

the catalog value.

 

 

 

 

 

 

 

 

 

 

2

11

Noise reduced by approx. 2 – 3 dB from

Approx. 1.2 hp

 

the catalog value.

 

 

 

 

 

 

 

 

 

 

3

10

Noise reduced by approx. 5 dB from the

Approx. 1.8 hp

 

catalog value.

 

 

 

 

 

 

 

 

 

*If Quiet mode is set, the capacity will begin to decrease during heating operation at low outdoor temperatures, when the outdoor air temperature is below standard conditions.

17-2. Anti-slime countermeasures ... EEPROM setting 0C (set only on the main unit)

This setting controls the operation of the drain pump.

Setting

0

1

2

3

Description

Normal control (setting at time of factory ship ment)

The drain pump operates for 20 minutes at 2-hour intervals.

The drain pump operates for 20 minutes at 20-minute intervals.

The drain pump operates constantly.

17-3. Delayed Start for Each System: Outdoor EEPROM 3E (set only on outdoor unit No. 1)

The operation start time can be delayed according to the set system addresses.

This setting reduces the voltage drop by preventing multiple systems from starting at the same time when opera- tion is restarted after multiple operating systems were stopped due to a power outage or other cause.

Setting

Effect

0No delayed start (setting at time of factory shipment)

1Start begins after [1 second x System address]

2Start begins after [2 seconds x System address]

3Start begins after [3 seconds x System address]

17-4. Automatic Backup: Outdoor EEPROM 48 (set only on outdoor unit No. 1)

Automatic backup is set to occur at the time the unit is shipped from the factory. However, the automatic backup function can be disabled by changing this setting to 1.

1 - 30

Page 35
Image 35
Sanyo CHDXR07263* Service Maintenance Functions, This setting controls the operation of the drain pump, Setting Effect