9.4UPS Shutdown (Daily)
①Press and / hold for 1 second.
| Buzzer |
| |
| Musical trill |
| |
| LEDs |
| |
Hold for 1 second.* | Green INPUT | Lit | |
Green INV.ON/STAND BY | Off | ||
| |||
| Green OUTPUT | Off |
Note
Do not touch MAIN SW when you perform a daily shutdown. Leave it set to the “ON” position.
*Note
The length of time to keep held down varies depending on the setting of item “⑨
switch response time” in §10.1 “Setup Menu Item List”. Operate as follows.
When “1 second” is selected: Hold for 1 second.
When “3 seconds” is selected: Hold for 3 seconds.
When “Special operation” is selected: Hold | for 3 seconds until the buzzer starts beeping, and then | |
hold | for 3 seconds more while the buzzer is beeping. |
9.5UPS Shutdown (If Not to Be Used for More Than a Week)
①Press and hold for 1 second.
| Buzzer |
|
| Musical trill |
|
Hold for 1 second.* | LEDs | Lit |
Green INPUT | ||
| Green INV.ON/STAND BY | Off |
| Green OUTPUT | Off |
② Set MAIN SW to the “OFF” position.
| All of the |
MAIN SW | LEDs go off. |
Set to “OFF”.EXT.
BATT
Note
If input power is shut off while the UPS is operating, the batteries are discharged the same as during an extended power outage. Be aware that when the input supply is restored, the full capacity of the
− 22 −