
2. For Proper Operation
(1)Make certain that the AC input voltage and frequency correspond to the specified equipment rating (100V, 110V, 115V, 120V, within
* The frequency variation range is set to ±3% when the UPS is shipped from the factory.
If the frequency variation range of input power supply is ±5%, select ±5% as described in item ③ “Frequency sync range” of 10.1 “Setup Menu Item List”. Because the frequency sync range is the same for both input and output, an input frequency error occurs when the frequency sync range exceeds the setting value, preventing the UPS from switching to active filter mode or economy mode operation.
(2)The current capacity of the AC power supply must satisfy the requirements of the UPS (0.96 kVA or more). (Breaker capacity of 20 A or more is recommended.)
2.2Installation Precautions(1)Carefully consider the leakage current when a leakage circuit breaker is installed on the input side. The maximum leakage current of the UPS is 3mA.
(2)Keep the UPS at least 1 m (about 40 inches) away from CRT displays. Other devices which may be sensitive to magnetic flux should be kept away from the UPS, as it emits a slight amount of magnetic flux.
(3)The UPS employs a fan for
When mounting the UPS in a rack, use a rack which allows ventilation and provide at least 20 cm (about 8 inches) clearance from the front and back of the rack to permit free airflow at the air intake and exhaust vents. Also, for maintenance purposes, a space of at least 1 m (about 40 inches) will be needed at the front of the rack, and a space of at least 50 cm (about 20 inches) will be needed at the back of the rack.
For details, see §6.3 “Installation Space”.(4)When the AC input power is
(5)As far as possible, do not ground the output (load) side. If you must make a
(1)Never
Do not connect laser printers, plain paper fax machines, copy machines, or overhead projectors as load devices. Such devices typically include heating elements that draw high current. This may cause an overload that could prevent battery backup operation when an outage occurs, and could damage the UPS.
(3)Power supply environmentIf the UPS is used in an environment subject to long and frequent power outages (more than once a week), the batteries may not receive sufficient charge, which could result in foreshortened battery life and premature battery failure.
(4)If the UPS is not operated for a long period, the batteries may require recharging. Operate the UPS with no load to recharge the batteries as indicated in the following table, according to the storage temperature. If the batteries in the UPS are left uncharged, their service life will be greatly foreshortened.
Storage Temperature | Charge Interval | |
25°C (77°F) | Once every 6 months | At least 20 hours |
30°C (86°F) | Once every 4 months | At least 20 hours |
40°C (104°F) | Once every 2 months | At least 20 hours |
− 6 −