You can exchange the batteries without stopping the load devices. However, this should be done as quickly as possible, because the UPS will be unable to provide backup power in the event of a power outage.
| ・ The battery pack weighs about 6kg (13.23 lbs). Be careful not to drop it on |
| your feet. Bodily injury can result. |
| ・ Wear insulated gloves and take other precautions when exchanging the |
| batteries. Otherwise electric shock can result. |
CAUTION | ・ There is a constant voltage (max. approx. 24V: approx. 12V ⋅ 2) at the |
| battery terminals. Do not touch them with your hands or short circuit them. |
| Bodily injury can result. |
①Remove the front panel of the UPS.
②Remove the screw on the right side of the battery cover, and then remove the battery
cover.
③Disconnect the battery connector.④ Pull the battery pack out.③ Battery connector. Insulate with tape or other insulator.
② Remove 1 screw*, and remove
the battery cover by sliding in the direction of the arrow.
①Remove by sliding in the direction of the arrow while firmly pressing the two locations indicated by ●
*Note for removing the screw
When a screw is used,
do not lose the removed screw.
When a
⑤ Insert the battery pack in the direction of the arrow.
⑥The connector cannot be inserted in the wrong orientation. Push in until you hear a click.
・The battery connector cannot be inserted in the wrong orientation. If it does not go in, do not try to force it. Doing so can damage the
CAUTION connector and result in electric shock.
・ Be careful not to get your hands caught when securing the cover.
− 28 −