10.User Settings

10.1Setup Menu Item List

You can configure the UPS by setting the menu items in the following list. Configure it according to your environment and requirements.

The controls and indicators on the control panel are used to set items in the Setup menu. For details, see §10.2 “Setup Menu Operations”.

Whenever you change a menu item setting, we recommend that you place a check mark in the “Current Setting” field of the Setup Menu Item List.

 

 

 

 

 

 

 

 

 

 

 

LED blinks

 

 

 

 

 

 

 

 

 

 

 

LED off

No.

Menu Item

Item Selection

Setting

Item Setting

Default

Current

 

Description

 

 

Notes

LEDs

LEDs

Setting

Setting

 

 

 

 

 

 

 

 

 

 

 

 

UPS operation mode

 

Auto

● ○ ○ ○

*

 

Switch the UPS operating mode

automatically.

● ○ ○ ○ ○

Double Conversion

○ ● ○ ○

 

 

Set the UPS operating mode to Double Conversion mode.

 

 

 

Economy

● ● ○ ○

 

 

Set the UPS operating mode to Economy mode

 

 

 

100V

● ○ ○ ○

Refer

 

100V setting (The default setting of Model: E11A102U001-00.)

Output voltage

○ ● ○ ○ ○

110V

○ ● ○ ○

to

 

110V setting (The default setting of Model: E11A102U001-10.)

(RESTART)

115V

● ● ○ ○

the

 

115V setting (The default setting of Model: E11A102U001-15.)

 

 

 

 

 

 

120V

○ ○ ● ○

right

 

120V setting (The default setting of Model: E11A102U001-20.)

 

Frequency sync range

 

1%

● ○ ○ ○

 

 

±1% allowance

 

Set the range (%) over which the output

● ● ○ ○ ○

3%

○ ● ○ ○

*

 

±3% allowance

 

frequency is adjusted to variations in the

 

(RESTART)

 

 

 

 

 

 

 

 

input frequency in Economy Mode and

 

 

5%

● ● ○ ○

 

 

±5% allowance

 

 

 

 

 

 

 

Active Filter Mode.

 

Battery startup

 

50Hz

● ○ ○ ○

 

 

50Hz setting

 

Set the inverter output frequency when

○ ○ ● ○ ○

 

 

 

UPS restarts from the batteries from

frequency

60Hz

○ ● ○ ○

*

 

60Hz setting

 

 

 

 

 

stopped status.

 

 

 

Do not use this setting.

● ○ ○ ○

 

 

 

 

 

 

 

 

 

Workstation

○ ● ○ ○

*

 

Setting for communications by the power management software over serial

PC Interface mode

● ○ ● ○ ○

 

or LAN connection.

 

 

 

 

 

 

 

 

 

 

 

Serial Login

● ● ○ ○

 

 

Shutdown by serial login.

 

 

 

 

 

 

Do not use this setting.

○ ○ ● ○

 

 

 

 

 

 

 

Serial baud rate

 

9600

● ○ ○ ○

*

 

Set the baud rate to 9600 bps.

Set the communications baud rate when

○ ● ● ○ ○

4800

○ ● ○ ○

 

 

Set the baud rate to 4800 bps.

a workstation, PC, or optional LAN card

 

 

 

2400

● ● ○ ○

 

 

Set the baud rate to 2400 bps.

is connected.

 

 

 

Auto

● ○ ○ ○

*

 

Auto restart

 

Specify when to restart the UPS after a

 

 

 

OFF

○ ● ○ ○

 

 

The UPS stays off.

 

 

Restart time

 

30%

● ● ○ ○

 

 

Same

behavior as Auto

when

power outage and shutdown of the UPS

● ● ● ○ ○

 

 

battery charge reaches 30%.

 

due to final discharge of the batteries.

 

 

 

 

(battery charge rate)

50%

○ ○ ● ○

 

 

Same

behavior as Auto

when

When 30%, 50%, or 80% is selected, the

 

 

 

 

 

battery charge reaches 50%.

 

UPS does not restart until the batteries

 

 

 

 

 

 

 

 

 

 

80%

● ○ ● ○

 

 

Same

behavior as Auto

when

are charged to the specified level.

 

 

 

 

 

battery charge reaches 80%.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All patterns

● ○ ○ ○

*

 

All sounds

 

 

 

Buzzer sound

○ ○ ○ ● ○

Pattern 1

○ ● ○ ○

 

 

Do not emit sounds on power outage, battery test, battery test abnormal and overload.

Pattern 2

● ● ○ ○

 

 

Emit alarm and key click sounds.

 

 

 

 

 

 

 

 

 

 

 

 

OFF

○ ○ ● ○

 

 

Emit key click sounds only.

 

 

 

 

 

 

1 second

● ○ ○ ○

*

 

Turn inverter off when pressed for 1 second.

Set the response time for

 

 

 

 

 

 

 

 

 

 

 

switch press to stop inverter

 

 

 

3 seconds

○ ● ○ ○

 

 

Turn inverter off when pressed for 3 seconds.

switch

● ○ ○ ● ○

 

 

power supply.

 

 

 

 

Turn inverter off on special operation. Select this setting to keep the

 

response time

 

Special operation

 

 

 

 

 

● ● ○ ○

 

 

inverter from being turned off by an accidental operation. See §9.4 "UPS

 

 

 

 

 

 

 

 

 

 

 

 

Shutdown (Daily)" for operation details.

 

 

Overload recovery

 

Auto return

● ○ ○ ○

*

 

Auto recovery with time

 

Set the conditions for automatic switch

○ ● ○ ● ○

 

 

back to inverter power supply (auto

 

 

 

 

 

 

 

operation

Bypass

○ ● ○ ○

 

 

Fixed as bypass on overload

 

return) after switching to bypass power

 

 

 

 

 

 

 

 

 

 

 

supply because of overload.

 

 

 

 

 

 

 

 

 

 

 

Inverter stop

 

OFF

● ○ ○ ○

*

 

The UPS stays off.

 

Specify the UPS operation during

● ● ○ ● ○

 

 

 

Operation (RESTART)

Bypass

○ ● ○ ○

 

 

Switch to bypass operation when

inverter power supply stops.

 

 

 

 

 

 

 

inverter stops.

 

 

 

 

 

 

Battery voltage level

● ○ ○ ○

*

 

When low battery voltage level is

 

 

 

Low battery voltage

 

 

detected.

 

Specify the timing for triggering the low

○ ○ ● ● ○

2 minutes

○ ● ○ ○

 

 

When remaining battery capacity

 

 

signal timing

 

 

is 2 minutes.

 

battery voltage signal.

 

 

 

3 minutes

● ● ○ ○

 

 

When remaining battery capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is 3 minutes.

 

 

 

 

 

 

5 minutes

● ○ ○ ○

*

 

5 minutes backup

 

Set the UPS backup time on power outage.

 

Battery backup time

 

15 minutes

○ ● ○ ○

 

 

15 minutes backup

 

An external battery must be connected for

● ○ ● ● ○

30 minutes

● ● ○ ○

 

 

30 minutes backup

 

settings of 15 minutes or higher.

 

 

 

60 minutes

○ ○ ● ○

 

 

60 minutes backup

 

(This item can’t take effect unless resetting

 

 

 

 

 

 

 

 

 

 

remaining battery life.)

 

 

 

180 minutes

● ○ ● ○

 

 

180 minutes backup

 

 

 

 

 

 

 

 

 

 

 

 

5 years

● ○ ○ ○

*

 

5 years lifetime type

 

Set the battery type. Set this when you

Battery type

○ ● ● ● ○

10 years

○ ● ○ ○

 

 

10 years lifetime type

 

exchange the battery or connect an external

 

 

 

battery. (This item can’t take effect unless

 

 

 

3 years

● ● ○ ○

 

 

3 years lifetime type

 

resetting remaining battery life.)

 

 

 

180 days

● ○ ○ ○

*

 

Check batteries every 180 days.

Set the interval (number of days) for the

Battery check schedule

● ● ● ● ○

90 days

○ ● ○ ○

 

 

Check batteries every 90 days.

automatic battery check. The check is

30 days

● ● ○ ○

 

 

Check batteries every 30 days.

carried out automatically when the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

specified number of days has elapsed.

 

 

 

None

○ ○ ● ○

 

 

No battery check.

 

 

 

 

 

 

 

 

 

 

Reset remaining

 

Do not reset

● ○ ○ ○

*

 

Do not reset.

 

 

 

○ ○ ○ ○ ●

 

 

 

 

Reset the battery information

(remaining life, accumulated battery

 

battery life

 

Reset

○ ● ○ ○

 

 

operating time, number of power outages, LED remaining life display),

 

 

 

 

 

 

 

when you exchange the battery.

 

 

Note

Changes to some menu items do not take effect until you restart the UPS. These items are indicated by (RESTART) in the "Menu Item" column. If a restart is required, be sure to power off the load devices before resetting. See §9.5 “UPS Shutdown (If Not to Be Used for More Than a Week)” for information about how to shut down the UPS, and §9.1 “UPS Startup (Normal Operation)” for information about how to start the UPS.