| Condition |
|
|
|
|
|
| Countermeasure |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| No recovery from utility |
|
| ・ Check whether | MAIN SW | on the back panel of the UPS is in the “ON” |
| ||||
|
|
| position. (If | MAIN SW | is set to the “OFF” position during normal |
| |||||
| power source failure. |
|
| operation, the same operation as for a utility power source failure will be |
| ||||||
| Utility power source |
|
| triggered.) See §9.1 “UPS Startup (Normal Operation)”. |
| ||||||
| failure occurs frequently. |
|
| ・ Verify that input voltage and input frequency are within the rated limits. |
| ||||||
|
|
|
| See §15.3 “Specifications”. |
| ||||||
|
|
|
| ・ Check whether the | Forced Bypass | switch is set to “Inverter”. This |
| ||||
|
|
|
| switch is located inside the front panel of the unit. Remove the front panel |
| ||||||
|
|
|
| to check. |
| ||||||
|
|
|
| See 14 “Maintenance Bypass Power Supply (Option)”. |
| ||||||
| UPS does not switch from |
|
| ・ When item ⑩ “Overload recovery operation” in §10.1 “Setup Menu Item |
| ||||||
|
|
| List” is set to “Auto return”: The UPS switches to inverter operation every |
| |||||||
| bypass operation to |
|
| 2.5 seconds, and switches back to bypass power supply if the overload |
| ||||||
| normal operation. |
|
| condition still persists. This cycle is repeated. |
| ||||||
|
|
|
| ・ When item ⑩ “Overload recovery operation” in §10.1 “Setup Menu Item |
| ||||||
|
|
|
| List” is set to “Bypass”: If the utility power voltage is low and the load |
| ||||||
|
|
|
| current is below the overload detection threshold when the UPS switches |
| ||||||
|
|
|
| to bypass power supply, the UPS continues to switch between inverter |
| ||||||
|
|
|
| power supply and bypass power supply. |
| ||||||
|
|
|
| ・ A battery test cannot be performed when: |
| ||||||
|
|
|
| ① Inverter is stopped. |
| ||||||
|
|
|
| ② Bypass power supply is active. |
| ||||||
| Cannot perform battery |
|
| ③ Input voltage or input frequency is out of range. |
| ||||||
| test. |
|
| ④ Shutdown under remote control is in progress. |
| ||||||
|
|
|
| ⑤ Equipment is defective. |
| ||||||
|
|
|
| ⑥ When the LODE LEVEL indicators are all off (load factor is less than |
| ||||||
|
|
|
| 20%) in the economy mode operation or the active filter mode operation. |
| ||||||
|
|
|
|
|
| ||||||
|
|
|
| ・ Verify that item ⑤ “PC Interface mode” in §10.1 “Setup Menu Item List” |
| ||||||
| Serial communication |
|
| is set to “Workstation”. Check the serial connection. See §5.3 “External |
| ||||||
|
|
| Interfaces”. |
| |||||||
| fails. |
|
|
| |||||||
|
|
| ・ Check the setting of item ⑥ “Serial baud rate” in §10.1 “Setup Menu Item |
| |||||||
|
|
|
|
| |||||||
|
|
|
| List”. The factory default setting of this item is “9600”. |
| ||||||
|
|
|
|
|
| ||||||
| Automatic inverter restart |
|
| ・ Check the setting of item ⑦ “Restart time (battery charge rate)” in §10.1 |
| ||||||
|
|
| “Setup Menu Item List”. Automatic inverter restart does not occur if this |
| |||||||
| does not occur after |
|
|
| |||||||
|
|
| item is set to “OFF”. |
| |||||||
| shutdown due to battery |
|
|
| |||||||
|
|
| If this item is set to “30%”, “50%”, or “80%”, the UPS does not start until |
| |||||||
| exhaustion following |
|
|
| |||||||
|
|
| the batteries are charged to the specified level. |
| |||||||
| power outage. |
|
|
| |||||||
|
|
| The factory default setting of this item is “Auto”. |
| |||||||
|
|
|
|
| |||||||
| Green DOUBLE |
|
| ・ The UPS is switching frequently between operating modes because the |
| ||||||
| CONVERSION and green |
|
| utility power is unstable. Set the UPS operating mode to “Double |
| ||||||
| ECONOMY light and go |
|
| Conversion Mode”. For details, see item ① “UPS operation mode” in §10.1 |
| ||||||
| off frequently at irregular |
|
| “Setup Menu Item List”. |
| ||||||
| intervals. |
|
| The factory default setting of this item is “Auto”. |
|
− 32 −