| Always power the UPS off before exchanging the fuse. Failure to do so can |
| cause electric shock. |
CAUTION | Be careful to avoid injury or electric shock. |
|
|
If the bypass fuse blows, the red ALARM indicator lights and output from the output terminals stops.
Proceed as follows to exchange the fuse for a new fuse, using the supplied bypass fuse.
①Stop the inverter by pressing and holding it for 1 second, and then setMAIN SW to “OFF”.
②Remove the fuse on the back panel of the UPS by pushing it in with a minus screwdriver and turning it in the counterclockwise direction.
③Insert the new fuse, and return it to the original location by turning it in the clockwise direction.
④ Set MAIN SW to “ON”, and then start the UPS by pressing | and holding it for |
1 second. |
|
UPS back panel
Bypass fuse
EXT.
BATT
MAIN SW
Note
・If you exchange the bypass fuse while the UPS is powered on, the red ALARM indicator will remain lit until you power the UPS off. Always power the UPS off before exchanging the fuse.
・Discard the old fuse as
This completes the fuse exchange.
− 30 −