Appendix Usage notes for SANUPS SOFTWARE STANDALONE

When using supplied “SANUPS SOFTWARE STANDALONE”, please note the following instructions.

“Charge” on the main screen of “SANUPS SOFTWARE STANDALONE”

For the charge rate (as a %) of the battery displayed on the main screen of “SANUPS SOFTWARE STANDALONE”, please note the followings.

Refer to §6.1 “Main Screen” in the User Guide of SANUPS SOFTWARE STANDALONE for details.

1.Proceed as follows to charge the batteries of the UPS for 12 hours or more at initial startup of the UPS.

Perform this operation before powering the connected load devices on.

Verify that the battery connector is connected correctly.

See §6.4 “Preparation Before Installation” in the E11A Instruction Manual for details.

Perform step “§9.1 ” in the E11A Instruction Manual.

Verify that the Green INPUT LED on the UPS control panel lights. Charging starts automatically.

Keep the UPS in the condition of step for 12 hours or more.

2.If the UPS is stopped and then restarted, even when the UPS is charged by step 1, “Charge” might be displayed as “80%” or “90%” not “100%” on the main screen. This occurs owing to the operating conditions such as ambient temperature.

However after normal operation of the UPS for 1 or 2 hours, “Charge” is displayed properly.

3.Connect the battery connector correctly. If the UPS is operated without the batteries, “Charge” is not displayed properly. Moreover, even if the battery connector is reconnected and operates the UPS, the proper charge rate is not displayed immediately.

After normal operation of the UPS for 12 hours or more, “Charge” is displayed properly.

4.Display of “Charge” is only an approximation. An actual charge rate of the battery might be different.

“Backup Time” on the main screen of “SANUPS SOFTWARE STANDALONE”

For the presumed “Backup Time” (in minutes) displayed on the main screen of “SANUPS SOFTWARE STANDALONE”, please note the followings.

Refer to §6.1 “Main Screen” in the User Guide of SANUPS SOFTWARE STANDALONE for details.

1.In §6.4 (1) “Setting the shutdown trigger conditions”, if “When the battery-low occurs, shutdown execution” is selected as the shutdown trigger conditions, set the time more than 40% of the presumed backup time displayed on the main screen.

Refer to §6.4 “Setting the Shutdown Conditions” in the User Guide of SANUPS SOFTWARE STANDALONE for details.

2.If the “Load” displayed on the main screen is less than 30%, the presumed backup time sometimes shows improper value. Therefore “When the battery-low occurs, shutdown execution” feature is not recommended to use with such a low load factor condition.

3.The presumed backup time is only an approximation. An actual backup time might be different.