| Item | Standard or Performance | Notes |
| |||||
|
| ||||||||
| Output capacity | 1kVA/0.7kW |
|
| |||||
| Cooling system | Forced air cooling |
|
| |||||
| Phases | Single phase, |
|
| |||||
|
|
|
|
| 100,110,115,120V |
|
| ||
| Voltage | User settable |
| ||||||
input | ±5% Economy /Active Filter mode operation | (Rated voltage same as output voltage) | |||||||
|
|
|
| ||||||
|
|
|
| ±10% Economy mode setting |
|
| |||
|
|
|
|
|
|
| |||
AC |
|
|
|
|
|
| ±8%: Double Conversion mode operation | ||
Frequency | 50Hz or 60Hz | ±1, 3, 5%: Economy /Active Filter mode | |||||||
| |||||||||
|
|
|
|
|
|
| operation |
| |
| Power requirements | 0.9kVA | Max. capacity during battery charging | ||||||
| Input power factor | 0.95 or more | During rated output | (*2) | |||||
| Phases | Single phase, |
|
| |||||
| Voltage | 100, 110, 115, 120V | User settable |
| |||||
| Voltage regulation | Rated voltage ±2% |
|
| |||||
| Rated frequency | 50Hz or 60Hz | Same as input frequency |
| |||||
| (auto selection) |
| |||||||
|
|
|
|
|
|
|
| ||
| Frequency regulation | Rated frequency ±1%: Double Conversion mode Setting | 1, 3, 5% selectable |
| |||||
| Rated frequency ±1, 3, 5%: Economy/Active Filter | Internal oscillator accuracy ±0.5% |
| ||||||
|
|
|
|
|
| mode operation |
| ||
|
|
|
|
|
|
|
| ||
| Voltage waveform | Sine wave |
|
| |||||
| Distortion factor of | Linear load: 3% or less | During rated output |
| |||||
Output | voltage waveform | 100% rectifier load: 7% or less |
| ||||||
|
| ||||||||
|
|
| change |
|
| switch |
| ||
|
|
|
| Rapid load |
|
| 0% ⇔ 100% at transient or output |
| |
AC | Transient |
|
|
|
|
|
|
| |
| Power outage, | Rated voltage | During rated output |
| |||||
| voltage |
|
| recovery |
| ||||
| variation |
|
| ±5 % |
|
| |||
|
|
|
|
|
| ||||
|
|
|
| Rapid input |
|
| ±10% variation |
| |
|
|
| voltage change |
|
|
| |||
|
|
|
|
|
|
| |||
| Response time | 5 cycles or less |
|
| |||||
| Load power factor (lag) | 0.7 (lag) | Variation range 0.7 (lag) to 1.0 |
| |||||
| Overcurrent protection | Auto switch to bypass circuit at 105% or more | With auto return function |
| |||||
| Overload |
| Inverter | 105% | 200ms |
| |||
|
|
|
|
|
|
| |||
| capability |
| Bypass | 200% | 30 seconds |
| |||
|
| 800% | 2 cycles |
| |||||
|
|
|
|
|
| ||||
Batteries |
| Type | Small sealed lead battery |
|
| ||||
Rated capacity | 10 A・h | (equivalent) | At 25°C (77°F) ambient temperature, | ||||||
| 20 hour ratio |
| |||||||
| Number | 2 (12V per battery) | 2 in direct series |
| |||||
| Backup time | 5 minutes (700W) | 10 minutes (500W) | rated load |
| ||||
|
|
|
|
|
|
|
| ||
| Generated heat | 50W |
|
| |||||
| Input leakage current | 3mA or less |
|
| |||||
| Operating environment | Ambient temperature: 0 to 40°C (32 to 104°F) | (*3) |
| |||||
| Relative humidity: 20 to 90% |
| |||||||
|
|
|
|
|
|
| |||
| Acoustic noise | 40 dB or less | 1 m (approx. 40 inches) from UPS front | ||||||
| panel, 'A' characteristics (linear load) | ||||||||
|
|
|
|
|
|
|
(*1): The inverter is capable of operation synchronized with AC input and instantaneous switchover provided that the AC input frequency is within ±3% (or 1%, 3%, 5%, selectable) of the rated frequency, and the AC input voltage is within +15%
The UPS enters battery operation with the AC input frequency is outside the specified range.
(*2): When input voltage waveform distortion is under 1%.(*3): The UPS contains batteries. Battery service life will be foreshortened if the UPS is used in an environment where the ambient temperature exceeds 30°C (86°F).
(*4): If grounded, the ground phase of the input and output must match according to UPS specifications.
(*5): The above table lists standard specifications. Some specifications are different for units with long backup times. For details, refer to the external battery specification instruction manual.
− 39 −