Download 85 pages 37.36 Kb
Page 15
Image 15
4. REFRIGERANT FLOW DIAGRAM

4. REFRIGERANT FLOW DIAGRAM

4-1. Refrigerant Flow Diagram

Indoor Unit SAP-KRV94EHDX

Outdoor Unit SAP-CRV94EHDX

SAP-KRV124EHDX

SAP-CRV124EHDX

Indoor unit

Outdoor unit

 

Wide tube

Accumulator

Compressor

 

 

 

 

 

 

Wide tube

service

 

 

 

valve

 

 

 

 

Muffler

4-way

 

 

O.D.

valve

 

 

 

 

 

9.52 mm

 

 

 

 

(3/8 ")

 

 

 

 

exchangerHeat

 

2-way

S

exchangerHeat

 

 

 

 

 

valve

 

 

 

 

 

 

Modulator

 

Capillary

 

 

 

 

tube for

 

 

Narrow

Electric split flow

 

expansion

 

tube

 

valve

 

service

Narrow tube

M

valve

O.D.Strainer Muffler

6.35mm

(1/4")

Cooling cycle

Heating cycle

Defrosting cycle

Insulation of Refrigerant Tubing

IMPORTANT

Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm.

 

Insulation

Thickness:

Thickness:

Min. 8 mm

Min. 8 mm

CAUTION

After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.

Narrow tube

Wide tube