7. INSTALLATION INSTRUCTIONS

7. INSTALLATION INSTRUCTIONS

7-1. Installation Site Selection

7-1-1. Indoor Unit

WARNING

To prevent abnormal heat

generation and the possibility

 

 

 

of fire, do not place obstacles,

 

enclosures and grilles in front

 

of or surrounding the air

 

conditioner in a way that may

 

block air flow.

5 cm

15 cm min.

5 cm

 

 

min.

min.

 

 

 

AVOID:

7-1. Installation Site Selection direct sunlight.

7-1-1. Indoor Unit nearby heat sources that may affect performance of the unit.

Manual background areas where leakage of flammable gas may be expected.

Manual background places where large amounts of oil mist exist.

DO:

Manual background select an appropriate position from which every corner of the room can be uniformly cooled. (High on a wall is best.)

 

Front View

 

 

Fig. 1

INDOOR

 

Tubing length (L)

UNIT

 

 

Elevation

 

OUTDOOR

difference (H)

UNIT

 

 

Fig. 2

Manual background select a location that will hold the weight of the unit.

Manual background select a location where tubing and drain hose have the shortest run to the outside.

Manual background allow room for operation and maintenance as well as unrestricted air flow around the unit. (Fig. 1)

Manual background install the unit within the maximum elevation difference (H) above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in Table 1 and Fig. 2.

CAUTION

For stable operation of the air conditioner, do not install wall-mounted type indoor units less than 1.5 m from floor level.

Indoor unit

Wall

Minimum height from floor level

1.5 m

Manual background Install the indoor unit more than 1 meter away from any antenna or power lines or connecting wires used for television, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation.

Table 1

Floor level

Fig. 3

 

Max. Allowable Tubing

Limit of Tubing

Limit of Elevation

Required Amount of

Model

Length at Shipment

Length (L)

Difference (H)

Additional Refrigerant

 

(m)

(m)

(m)

(g/m)*

KRV94 / 124

7.5

15

10

15

 

 

 

 

 

*If total tubing length becomes 7.5 to 15 m, charge additional refrigerant (R410A) by 15 g/m. No additional charge of compressor oil is necessary.