Sanyo SAP-KRV94EHDX service manual Checking the Indoor and Outdoor Units

Models: SAP-KRV94EHDX

1 85
Download 85 pages 37.36 Kb
Page 45
Image 45
10-3. Checking the Indoor and Outdoor Units

(2)If the self-diagnostics function fails to operate

Check the indoor unit.

Is the fuse blown?

Normal

Replace the controller.

No indicators illuminate and the indoor fan does not rotate.

Check the power voltage.

Blown

Replace the circuit board or the fuse.

10-3. Checking the Indoor and Outdoor Units

(1) Checking the indoor unit

No.

Control

Check items (unit operation)

 

 

 

1

Press EMERGENCY OPERATION button

The rated voltage must be present between inter-unit wirings 1 and 2.

 

of main unit controller, or start operation

Connect a 5 kohm resistor between inter-unit cables 2 and 3. When the

 

using the remote controller.

voltage at both ends is measured, approximately 12 to 15 V DC must

2

 

be output and the multimeter pointer must bounce once every 8

Press and hold the TEST RUN button

seconds.

 

on the main unit controller until the buzzer

Or instead of measuring the voltage, you can insert an LED jig and

 

sounds 1 time.

check that the LED flickers once every 8 seconds.

 

 

 

Manual background If there are no problems with the above, then check the outdoor unit.

(2) Checking the outdoor unit

No.

Control

Check items (unit operation)

 

 

 

1

Apply the rated voltage between outdoor

The control panel LED (red) must illuminate.

 

unit terminals 1 and 2.

 

 

 

 

2

Short-circuit the outdoor unit COM terminal

The compressor and fan motor must turn ON about 5 seconds later

 

to the T-RUN terminal.

after the terminals are shorted.

 

 

 

Manual background If there are no problems with the above, then check the indoor unit.

TEST/MV T-RUN terminals

Manual background Using the TEST/T-RUN terminals

T-RUN : Test run (compressor and fan motor turn ON).

TEST/MV : Compresses time to 1/60th (accelerates operation by 60 times faster than normal). Fully opens the electric expansion valve.

Circuit board

TEST/MV T-RUN COM

(3) Checking the serial communications

 

 

Control 1

 

Control 2

 

.... OFF

.... Blinking

.... Illuminated

Initial self-diagnostics

Short-circuit terminals 2 and 3 on

Short-circuit terminals 2 and 3 on

 

 

the indoor unit terminal plate.

the outdoor unit terminal plate.

 

 

 

 

 

Probable location of malfunction

Ion

Timer

Operation

Ion

Timer

Operation

Ion

Timer

Operation

 

 

( 3 )

( 2 )

( 1 )

( 3 )

( 2 )

( 1 )

( 3 )

( 2 )

( 1 )

 

 

 

 

 

 

 

 

 

 

 

Indoor unit circuit board failure

 

 

 

 

 

 

 

 

 

Outdoor unit circuit board failure

 

 

 

 

 

 

 

 

 

Failure (open circuit, contact failure, etc.)

 

 

 

 

 

 

 

 

 

in the inter-unit wirings

 

 

 

 

 

 

 

 

 

 

Outdoor unit circuit board failure

Manual background Turn the power OFF before performing short circuiting work.

Manual background During the self-diagnostics check, the check results are the first indication when the TEST RUN button is pressed until the buzzer sounds 1 time, after the power supply is ON.

Manual background So that the check can be made quickly, indicators blink at first communication after power ON.

Manual background Before performing the above checks, press the ON/OFF operation button of indoor unit or remote controller to operate the air conditioner, and check that AC 220 to 240V is output to terminals 1 and 2. If it is not output, there is a failure related to the indoor unit power.

45