10. TROUBLESHOOTING

10-1. Precautions before Performing Inspection or Repair

After checking the self-diagnostics monitor, turn the power OFF before starting inspection or repair.

High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter).They retain an electrical charge (charging voltage DC 310 V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be careful not to touch any electrified parts before the controller LED (red) turns OFF.

If the outdoor controller is normal, approximately 30 seconds will be required for the charge to dissipate. However, allow at least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller.

After repairs are carried out, be sure to press and hold the TEST RUN button until the buzzer sounds 2 times to erase the diagnosis results.

10-2. Method of Self-Diagnostics

If the indoor unit operation lamp is blinking every 0.5 seconds, follow the procedure below to perform detailed trouble diagnostics.

NOTE

1.If the operation lamp blinks every 0.5 seconds immediately when the power is turned ON, there is an external ROM (OTP data) failure on the indoor circuit board or ROM socket insertion problem, or the ROM has not been installed. Make sure the ROM is in existence.

2.The failure mode is stored in memory even when the power is not ON. Follow the procedure below to perform diagnostics.

Main unit controller

TEST RUN button

ON/OFF operation button

PROCEDURE

1.Turn the power supply switch ON. However, the A/C itself should remain stopped.

2.Press and hold the TEST RUN button on the main unit controller until the buzzer sounds 1 time. At this time, releasing the TEST RUN button starts self-diagnostics.

3.If there is a sensor failure or a protective function has activated, self-diagnostics lamps 1, 2, and 3 will illuminate in the following pattern: 5 seconds blinking (illuminated) + 2 seconds OFF. (Buzzer sounds once while lamps are OFF.)

NOTE If there is no trouble, then self-diagnostics lamps 1, 2, and 3 do not illuminate, and the buzzer does not sound.

4.Diagnostics is completed when the buzzer sounds 3 times.

<IMPORTANT> After repairs are carried out, be sure to press and hold the TEST RUN button until the buzzer sounds 2 times. When the TEST RUN button is released, the buzzer sounds 1 long beep, and the diagnosis results are erased.

43

Page 43
Image 43
Sanyo SAP-KRV94EHDX Troubleshooting, Precautions before Performing Inspection or Repair, Method of Self-Diagnostics

SAP-KRV94EHDX specifications

The Sanyo SAP-KRV94EHDX is a cutting-edge split-type air conditioning unit that exemplifies advanced technology and efficiency. Designed for both residential and commercial spaces, this model is equipped with features that cater to various cooling and heating needs.

One of the main highlights of the Sanyo SAP-KRV94EHDX is its energy efficiency. With a high Energy Efficiency Ratio (EER), this unit minimizes energy consumption while maximizing cooling performance. This not only results in lower electricity bills but also contributes to a reduced carbon footprint, making it an environmentally friendly choice for users.

The SAP-KRV94EHDX employs inverter technology, which allows the compressor to adjust its speed dynamically based on the temperature requirements of the environment. This means that the unit operates more quietly and uses less energy when maintaining a consistent temperature. The inverter system ensures that the air conditioner can quickly reach the desired cooling or heating temperature and maintain it without the frequent on-off cycles typical of traditional units.

Additionally, the air conditioning unit comes with a powerful cooling capacity, effectively managing larger spaces. It can easily handle varying ambient conditions while providing rapid cooling in extremely warm weather, making it perfect for areas with hot climates.

Other notable features include a user-friendly remote control, allowing users to adjust settings from a distance effortlessly. The unit also incorporates a multi-stage air filtration system designed to remove dust, allergens, and other airborne particles, contributing to better indoor air quality.

The Sanyo SAP-KRV94EHDX is not just about functionality; it also boasts a sleek and modern design that blends seamlessly with various interior aesthetics. Its quiet operation ensures that it does not disturb daily activities, making it suitable for bedrooms, offices, and living spaces.

Moreover, the unit comes with various operational modes, including cooling, dehumidification, and a heating function. This versatility makes the SAP-KRV94EHDX an all-season solution for climate control.

In summary, the Sanyo SAP-KRV94EHDX is a top-tier air conditioning unit that combines efficiency, advanced technology, and user convenience. Its inverter technology, multi-stage air filtration, and modern design make it a reliable choice for anyone seeking comfort throughout the year.