10. TROUBLESHOOTING
After checking the
If the outdoor controller is normal, approximately 30 seconds will be required for the charge to dissipate. However, allow at least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller.
After repairs are carried out, be sure to press and hold the TEST RUN button until the buzzer sounds 2 times to erase the diagnosis results.
10-2. Method of Self-Diagnostics
If the indoor unit operation lamp is blinking every 0.5 seconds, follow the procedure below to perform detailed trouble diagnostics.
NOTE
1.If the operation lamp blinks every 0.5 seconds immediately when the power is turned ON, there is an external ROM (OTP data) failure on the indoor circuit board or ROM socket insertion problem, or the ROM has not been installed. Make sure the ROM is in existence.
2.The failure mode is stored in memory even when the power is not ON. Follow the procedure below to perform diagnostics.
Main unit controller
TEST RUN button
ON/OFF operation button
PROCEDURE
1.Turn the power supply switch ON. However, the A/C itself should remain stopped.
2.Press and hold the TEST RUN button on the main unit controller until the buzzer sounds 1 time. At this time, releasing the TEST RUN button starts
3.If there is a sensor failure or a protective function has activated,
NOTE If there is no trouble, then
4.Diagnostics is completed when the buzzer sounds 3 times.
<IMPORTANT> After repairs are carried out, be sure to press and hold the TEST RUN button until the buzzer sounds 2 times. When the TEST RUN button is released, the buzzer sounds 1 long beep, and the diagnosis results are erased.
43