Hardware setup

Characteristics and functions of the terminals

Terminal

Function

Electrical characteristics

R2A

Configurable relay outputs:

• Minimum switching capacity: 10 mA for 5 V c

R2B

1 relay logic output, one “N/C”

• Maximum switching capacity on resistive load (cos ϕ = 1 and L/R = 0 ms):

R2C

contact and one “N/O” contact

5 A for 250 V a and 30 V c

 

with common point.

• Maximum switching capacity on inductive load (cos ϕ = 0.4 and L/R = 7 ms):

 

 

2 A for 250 V a and 30 V c

 

 

• Sampling time: 8 ms

 

 

• Service life: 100,000 operations at maximum switching power

COM

Analog I/O common

0 V

+10

Power supply for reference

• +10 V (+ 8% - 0%)

 

potentiometer (2.2 to 10 kΩ)

• 10 mA max

 

 

• Protected against short-circuits and overloads

AI2

Analog voltage input

Bipolar analog input 0 ± 10 V (maximum safe voltage ± 30 V)

 

 

The + or - polarity of the voltage on AI2 affects the direction of the setpoint and

 

 

therefore the direction of operation.

 

 

• Impedance: 30 kΩ

 

 

• Resolution: 0.01 V, 10-bit + sign converter

 

 

• Precision ± 4.3%, linearity ± 0.2%, of maximum value

 

 

• Sampling time: 8 ms

 

 

• Operation with shielded cable 100 m maximum

AI3

Analog current input

Analog current input X-Y mA by programming X and Y from 0 to 20 mA:

 

 

• Impedance: 250 Ω

+24

Logic input power supply

• + 24 V protected against short-circuits and overloads, minimum 19 V, maximum 30 V

 

 

• Maximum customer current available: 100 mA

LI1

Logic inputs

Programmable logic inputs

LI2

 

• Impedance: 3.5 kΩ

LI3

 

• + 24 V internal or 24 V external power supply (min. 19 V, max. 30 V)

 

 

• Max. current: 100 mA

 

 

• Max. sampling time: 4 ms

 

 

Source position: Positive logic State 0 if < 5 V or logic input not wired, state 1 if > 11 V

RJ45

Communication port

Connection for SoMove software, Modbus, remote display, loader tools.

SW1

Addressing switches

See page 14.

SW2

Line termination switches

See page 11.

PROFIBUS

Communication

PROFIBUS DP open style connector for connection to the fieldbus, see page 11.

DP

 

 