Diagnostics

Communication fault management

The behaviour of the drive in case of communication interruption is described in the ATV312 programming manual.

The communication between the master (external management system) and the drive is broken:

In this case, the drive will generate a (CnF) error message.

The communication card is not working properly:

In this case, the drive will generate a (COF) message.

 

 

Code

 

Name

 

Probable cause

 

Remedy

 

 

 

 

 

 

 

 

 

 

 

CFF

 

[INCORRECT

• The current configuration is

Return to factory settings or retrieve the backup

 

 

 

 

 

CONFIG.]

 

inconsistent.

 

configuration, if it is valid. See the [Restore config.]

 

 

 

 

 

 

• Addition or removal of an option

 

(FCS) parameter in ATV312 programming manual.

 

 

 

CnF

 

[NETWORK

• Communication detected fault on the

Check the environment (electromagnetic

 

 

 

 

 

FAULT]

 

communication card

 

compatibility).

 

 

 

 

 

 

 

 

Check the wiring.

 

 

 

 

 

 

 

 

Check the time out.

 

 

 

 

 

 

 

 

Replace the option card.

 

 

 

 

 

 

 

 

• See the [CANopen fault mgt] (COL) parameter in the

 

 

 

 

 

 

 

 

 

ATV312 programming manual to define the stop

 

 

 

 

 

 

 

 

 

mode with a (CnF).

 

 

 

COF

 

[CANopen FAULT]

Interruption in communication

Check the communication bus.

 

 

 

 

 

 

 

between the option card and the

Check the option card.

 

 

 

 

 

 

 

drive

 

 

 

 

 

ILF

 

[INTERNAL LINK

Interruption in communication

Replace the option card.

 

 

 

 

 

FAULT]

 

between the option card and the

 

 

 

 

 

 

 

 

 

drive

 

 

 

 

 

 

 

 

 

 

 

 

 

(CnF) [Network fault]: Option card fault code

This parameter is read-only and is only visible if an option card is present. The fault code remains saved in the parameter, even if the cause disappears. The parameter is reset after the drive is disconnected and then reconnected.

The values of this parameter is:

1: Time out on the reception of the periodic variables addressed to the drive

For the full list of the fault detected codes, see ATV312 programming manual on www.schneider-electric.com

S1A10386 10/2009

19

Page 19
Image 19
Schneider Electric 312 manual Communication fault management, Code Name Probable cause Remedy