Configuration

Control via PROFIBUS DP in native profile (CiA402)

The command and the target both come from PROFIBUS DP. Input LI3 at the terminals is used to switch between PROFIBUS DP and the terminals.

Control is in native profile (CiA402).

Configure the following parameters:

Parameter

Value

Comment

Profile

Combined native profile (CiA402)

The run commands are in native profile (CiA402), the command and the

 

 

target come from the same channel.

 

 

 

Target 1 configuration

Network card

Target 1 comes from PROFIBUS DP.

 

 

 

Target 2 configuration

Analog input 2 on the terminals

Target 2 comes from input AI2 on the terminals.

 

 

 

Target switching

Input LI3

Input LI3 switches the target (1 2) and the command.

 

 

 

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[COMMAND] (CtL-)

[Profile] (CHCF)

[Not separ.] (SIM)

 

 

 

 

[Ref.1 channel] (Fr1)

[Network] (nEt)

 

 

 

 

[Ref.2 channel] (Fr2)

[AI2] (AI2)

 

 

 

 

[Ref 2 switching] (rFC)

[LI3] (LI3) (1)

 

 

 

(1)LI4 to LI6 and AI1 are assignable in the menus but their value is allways forced to 0.

Control via PROFIBUS DP or the terminals in native profile (CiA402)

The command and the target both come from PROFIBUS DP or the terminals. Input LI3 at the terminals is used to switch between PROFIBUS DP and the terminals.

Control is in native profile (CiA402).

Configure the following parameters:

Parameter

Value

Comment

Profile

Combined native profile (CiA402)

The run commands are in native profile (CiA402), the command and the

 

 

target come from separate channels.

 

 

 

Target 1 configuration

Network card

Target 1 comes from PROFIBUS DP.

 

 

 

Target 2 configuration

Analog input 2 on the terminals

Target 2 comes from input AI2 on the terminals.

 

 

 

Target switching

Input LI3

Input LI3 switches the target (1 2) and the command.

 

 

 

Menu

Parameter

 

Value

[COMMAND] (CtL-)

[Profile] (CHCF) is configured in separate mode

[Separate] (SEP)

 

 

 

 

 

[Cmd channel 1]

(Cd1) Channel 1 is used with the communication

[Network] (nEt)

 

 

 

 

 

[Cmd channel 2]

(Cd2) Channel 2 is used with the terminal blocks

[Terminal] (tEr)

 

 

 

 

[Cmd switching] (CCS) LI3 is used for switching between channel 1 and 2

[LI3] (LI3) (1)

 

(see also the programming manual of the ATV312 for more details).

 

 

 

 

(1)LI4 to LI6 and AI1 are assignable in the menus but their value is allways forced to 0.

 

S1A10386 10/2009

17

Page 17
Image 17
Schneider Electric 312 manual Control via Profibus DP in native profile CiA402