Integration of the ATV312 in a PROFIBUS DP network controlled by a Modicon TSX P57 354M
The following chapter describes how to integrate an ATV 312 equipped with a VW3 A312 07 option module on a PROFIBUS DP based configuration.
PROFIBUS DP communication module:
Altivar 312 | Altivar 312 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TSX PREMIUM PLC
Connector with line
terminator
490 NAD 911 03
PROFIBUS DP connection
cable TSX PBS CAp00
(100 or 400 m)
Configuration of the communication
With Unity, cyclic exchanges between the PROFIBUS DP master (TSX Premium PLC + TSX PBY100 module) and the Altivar 312 take the form of input words %IWxy.0.k and output words %QWxy.0.k, where "x" = number of the PLC rack and "y" = location of the PROFIBUS DP module in the PLC rack.
PROFIBUS DP | PL7 output word | Altivar 312 | |
parameter | |||
|
| ||
PKW | %QWxy.0 | PKE | |
|
|
| |
| %QWxy.0.1 | R/W | |
| %QWxy.0.2 | Not used | |
| %QWxy.0.3 | PWE | |
|
|
| |
PZD1 | %QWxy.0.4 | CMD | |
PZD2 | %QWxy.0.5 | LFRD |
PROFIBUS DP | PL7 input word | Altivar 312 | |
parameter | |||
|
| ||
PKW | %IWxy.0 | PKE | |
|
|
| |
| %IWxy.0.1 | R/W/N | |
| %IWxy.0.2 | Not used | |
| %IWxy.0.3 | PWE | |
|
|
| |
PZD1 | %IWxy.0.4 | ETA | |
PZD2 | %IWxy.0.5 | RFRD |
Project configuration
The TSX Modicon PLCs can be used as PROFIBUS DP Master Device in association with the PBY 100 Profibus card.
Tree view of PLC configuration under a Unity project:
24 | S1A10386 10/2009 |