2.10 Default parameters

Function

Parameter

Default value

Possible value

 

 

 

 

Network

IP address

172.17.16.16

Network IP address

 

Subnet mask

255.255.0.0

Network IP address

 

Gateway Address

0.0.0.0

Network IP address

 

BOOTP/DHCP

Enabled

Active / Deactivated

 

Firmware Upload

Enabled

Active / Deactivated

 

SMTP server

smtpserver

49 characters maximum

 

 

 

 

System

UPS Contact

Computer Room Manager

49 characters maximum

 

UPS Location

Computer Room

31 characters maximum

 

History log interval (sec.)

60

10 to 99999 sec.

 

Environment log interval (sec.)

300

10 to 99999 sec.

 

Default Language

English

English / French / Spanish /

 

 

 

German / Italian

 

 

 

 

Manager table

 

empty

50 maximum

 

 

 

 

Access control

User name

MGEUPS

10 characters maximum

 

Password

MGEUPS

10 characters maximum

 

Community name read

public

49 characters maximum

 

Trap port

161

Non configurable

 

 

 

 

Date and time

Date and time adjustment

Manual adjustment

Manual adjustment

 

 

 

 

Serial link

Speed

9600 baud

Non configurable

 

Data bits

8

Non configurable

 

Stop bits

1

Non configurable

 

Parity

without

Non configurable

 

Flow control

without

Non configurable

 

 

 

 

 

 

 

 

Modbus/jbus

 

 

 

 

 

 

 

JBUS/MODBUS communication

- Baud rate

- 9600 bauds

- 1200, 2400, 4800, 9600

 

- Parity

- without parity

- Without parity, even parity

 

- Slave number

- Slave nr 1

- 1 to FF (hexadecimal)

 

 

 

 

RS232 link

- Link connection in transmit

- Rx on pin 1

- Rx on pin 1

 

data (Tx) or receive data (Rx)

- Tx on pin 3

- Tx on pin 3

 

 

 

 

RS485 link

- Termination

- No termination

- With or without (2 or 4 wires)

 

 

 

 

Teleservice

- TLS settings via RS232 Menu

- TLS for 1 UPS and Sensor

TLS up to 9 UPS

 

 

feature available

(1UPS/NMTC+ 9 UPS/INMC)

 

 

 

 

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 12/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com