6.2.4 Measurements

Click on "Measurements" in the menu

The following measurements are saved and time-stamped:

"AC Normal : Average voltage": Value of the utility average voltage supplying the UPS (1)

"AC Normal : Frequency": Value of the utility frequency supplying the UPS (1)

"AC Normal : Total current": Value of the utility total current supplying the UPS (1)

"AC Output : Average voltage": Value of the output average voltage of your UPS

"AC Output : Frequency": Value of the output frequency of your UPS

"AC Output : Power (kVA)": Value in kVA of the output power of your UPS for each phase

"AC Output : Power (kVW)": Value in kW of the output power of your UPS for each phase

"Battery : Capacity (%)": Percentage of charge available in the battery (1)

The save frequency of these values is defined in the "System" page (60 seconds by default). Approximately 435 time-stamps are stored permanently on the card. The oldest time-stamps are automatically deleted.

"Save Log" enables all saved values to be opened or saved in CSV format. (compatible with Excel type spreadsheets) "Clear Log" enables deletion of all records. Enter the login/password to validate this action.

(1): Value displayed is not sigficative with a Static Switch Cabinet unit.