Schneider Electric 66124, 66123 user manual Administration, Network, Environment sensor

Models: 66123 66124

1 98
Download 98 pages 55.32 Kb
Page 10
Image 10

2.4Administration

Up to 35 workstations protected by Network Shutdown Modules - Central or local configuration.

Up to 5 browsers connected at the same time (3 in SSL).

Minimum recommended browser versions: Internet Explorer 6.x / 7.0, Mozilla Firefox 1.5 / 2.0 / 3.0 E-mail sending configurable according to UPS alarms and transmission of a periodical report. Protection by encrypted password.

Protection by secure SSL connection. Saving of logs in the non-volatile memory. Languages available:

INMC 66123 : English / French / Spanish / German / Italian

NMTC 66124 : English

On-line help in English available for each page. Card firmware updated via the network

2.5Network

Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet.

The used ports are:

 

 

BootP

DHCP

UDP 68 , 67

HTML

TCP 80

 

SSL

TCP 443

 

NSM in connected mode

TCP 5000

 

SMTP

25

 

SNMP V1

161

 

TRAP SNMP

162

 

2.6Environment sensor

Temperature measurement from 0 to 70°C with +/- 1°C accuracy

Measurement of humidity from 0 to 100% with +/- 6% accuracy

Min / max time-stamped function for temperature and humidity

Choice of temperature readings in Celsius or Fahrenheit

High and low thresholds, hysteresis and offset adjustable via Web interface

Possibility of notification of status changes by e-mail, SMS or SNMP trap

Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m)

Name and status of each configurable contact

Recording of events and measurements in the card log

Possibility of shutting down the installation in the event of a threshold being exceeded or on opening / closure of a dry contact Connection to the card with straight CAT5 RJ45 network cables (maximum card/sensor distance: 20 m)

Hot installation

2.7MIB (Management Information Base)

Compatible with MIB MGE V1.8 adapted for Galaxy 7000.

The list of objects managed can be found in the chapter 8.2.

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 10/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

 

 

www.apc.com

 

 

Page 10
Image 10
Schneider Electric 66124, 66123 user manual Administration, Network, Environment sensor, MIB Management Information Base