Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 72/98
Network Management Teleservice Card
APC by Schneider Electric
www.apc.com
10.1.3 Configuration of the JBUS/MODBUS communication parameters
Connect the card to a computer equipped with a Hyper terminal type emulator. The serial link must be set at 9600 baud, 8 bits, no parity, 1 stop
bit, and without flow control.
Check that UPS power is on.
Enter the MGEUPS or mgeups password (non modifiable).
The next menu appears:
-----------------------------------------------------------------------------
MGE UPS SYSTEMS
NETWORK MANAGEMENT CARD
-----------------------------------------------------------------------------
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
5 : Jbus configuration
6 : Sensor configuration
0 : Exit
-----------------------------------------------------------------------------
Type 5 and return to display the JBUS configuration menu.
The next menu appears:
-----------------------------------------------------------------------------
Jbus settings
-----------------------------------------------------------------------------
1 : Display Jbus settings
2 : Modify Jbus settings
3 : Display Jbus diagnostics
4 : Reset Jbus diagnostics
5 : Return to Jbus Default Configuration
6 : Display Jbus frames
0 : Exit
-----------------------------------------------------------------------------