6.2.1.4 "UPS status" zone: Essential information

"Active sources": (available on parallel or modular UPS) X UPS + Y redundant + Z PSM:

X indicates the minimal number of UPS necessary to power the load,

Y indicates the number of UPS in redundancy.

Z indicate the number of UPS in PSM (Power Saving Mode)

An alarm can be generated if the number of UPS in redundancy is less than a configurable threshold. See UPS modules section.

"Power source": indicates whether the power comes from the AC normal input or from the UPS battery

"Output load level": indicates the power percentage used at UPS output "Output" indicates if the UPS output is powered

The various icons showing the status of the UPS outputs are:

Output powered

Output not powereded

Battery Information :

"Battery load level": battery charge level in percent

The information is completed with the two following labels:

Charging” : if the utility power is present and the battery charge is in progress

Discharging”: if the UPS operates on battery.

Fault”: if the battery is faulty.

"Remaining backup time": Estimation of the battery's maximum backup time remaining before UPS shutdown

"Battery status": Result of the last automatic battery test carried out by the UPS Possible values are:

OK: the test was completed correctly

NOK: the battery needs to be checked

Deactivated: the automatic battery test is not validated on the UPS