Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 77/98
Network Management Teleservice Card
APC by Schneider Electric
www.apc.com
Status description Status to 0 Status to 1 Word
hex
Bit
0 - F
Status Familly
for
BMS design
AC bypass thermal overload (Nota 7) No yes 46 6 Minor Fault
AC Bypass out of tolerance (Nota 7) No yes 46 7 Major Warning
AC bypass frequency out of tolerance (Nota 7) No yes 46 9 Minor Warning
AC bypass voltage out of tolerance (Nota 7) No yes 46 A Minor Warning
AC bypass switch (Q4S) Open Closed 46 E Status
Static switch major fault (Nota 7) absent present 47 0 Minor Fault
Inverter desynchronized with AC bypass absent present 47 1 Status
Output switch (Q5N) Open Closed 47 B Status
Charger major fault No Yes 49 0 Minor Fault
Battery charging (Nota 5) No Yes 49 3 Status
Inverter major fault (Nota 5) No Yes 4C 1 Minor Fault
Inverter overload (Nota 5) No Yes 4C 2 Major Warning
Inverter thermal overload (Nota 5) No Yes 4C 3 Minor Fault
Inverter limitation (Nota 5) No Yes 4C 4 Status
UPS fuse fault (Nota 5) absent Present 4C 5 Minor Fault
Load Short circuit absent Present 4F 1 Minor Fault
Nota 1 : for Battery charge it is necessary to set 2 bits, for legacy JBUS table
Nota 3 : switch status equal 1, when closed
Nota 4 :
INMC/NMTC
Galaxy @41 Hex @41 Bin @41 Bit3 @41 Bit2 @41 Bit1 @41 Bit 1, 2 and 3 in Dec
Unitary 2 0010 0 0 1 1
Modular 4 0100 0 1 0 2
Parallel 6 0110 0 1 1 3
SSC 8 1000 1 0 0 4
Nota 5 : This Information is not present with a Static Switch Cabinet unit.
Nota 6 : Device Ventilation Fault is present only in a Static Switch Cabinet 800kVA, this information is not present in a Static Switch Cabinet
1200kVA
Nota 7 : For a configuration with UPS in parallel with SCC unit, the Main 2 data need to read on the card installed in the SSC unit.
Nota 8 : Available with NMC firmware 808 and UPS package AN
Nota 9 : Available with NMC fw 808 and G7000 package AM