10.3.4.5 UPS on Bypass due to End of battery runtime

 

 

 

 

Modbus

 

 

 

 

Status

 

 

Address

Value

 

 

 

 

 

 

(word +

 

 

 

 

 

 

 

bit)

 

 

 

 

Main UPS status

 

 

 

 

 

 

 

Load Powered

 

400

1

 

 

 

Load on inverter

 

401

0

 

 

 

UPS on battery

 

404

0

 

 

 

Load on AC Bypass

 

407

1

 

 

 

UPS in maintenance position

 

461

0

 

 

 

Battery Charging

 

493

0

 

 

 

UPS in Power Saving Mode

 

 

41B

0

 

 

 

Nota: Available with NMC fw 808 and G7000 package AM

 

 

 

 

 

 

 

 

 

 

 

 

Breaker status

 

 

 

 

 

 

 

Q5N circuit breaker

 

 

47B

1

 

 

 

Q1 circuit breaker

 

443

1

 

 

 

Q4S circuit breaker

 

 

46E

1

 

 

 

QF1 circuit breaker

 

 

42F

1

 

 

 

Q3BP circuit breaker

 

416

0

 

 

 

UPS Fault

 

 

 

 

 

 

 

UPS general alarm - Red Led from UPS HMI

 

402

1

 

 

 

Nota: Available with NMC fw 808 and G7000 package AN

 

 

 

 

 

 

 

Load not protected

 

 

41A

1

 

 

 

UPS Internal Communication Fault

 

409

0

 

 

 

Rectifier fault

 

419

0

 

 

 

Rectifier (PFC) fuse fault

 

449

0

 

 

 

Battery temperature fault

 

 

42A

0

 

 

 

End of battery runtime

 

406

1

 

 

 

Emergency Power Off

 

 

40B

0

 

 

 

Fan Faillure

 

 

40E

0

 

 

 

UPS Warning

 

 

 

 

 

 

 

Orange Led from UPS HMI

 

 

41C

1

 

 

 

Nota: Available with NMC fw 808 and G7000 package AN

 

 

 

 

 

 

 

Overload

 

 

40A

0

 

 

 

Low battery WARNING

 

405

1

 

 

 

Inverter Overload

 

 

4C2

0

 

 

 

Static switch overload

 

465

0

 

 

 

AC Normal Frequency Out Of Tolerance

 

 

44B

1

 

 

 

AC Normal Voltage Out Of Tolerance

 

448

1

 

 

 

AC bypass Out of tolerance

 

467

0

 

 

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 85/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com

Page 85
Image 85
Schneider Electric 66123, 66124 user manual UPS on Bypass due to End of battery runtime