Ethernet port

LED

Colour

Activity

Description

 

 

 

 

 

 

 

 

 

 

ACT

Green

Off

Card not connected to the network.

 

 

On

Card

connected to

the

network

but

 

 

 

without activity

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing

Port

is

active

in

receiving

/

 

 

 

transmission

 

 

 

 

 

 

 

 

 

 

 

100M

Orange

Off

Port operating at 10Mbits/s.

 

 

 

On

Port operating at 100Mbits/s.

 

Service port (Settings/Sensor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED

Colour

Activity

Description

 

 

 

 

UPS

Green

Off

Card startup in progress.

 

Data

 

On

Communication with UPS in progress

 

 

 

 

Normal operation.

 

 

 

 

 

Flashing

 

Communication with the UPS is

 

 

 

 

 

 

operational

 

 

 

RS232

Orange

Off

Configuration menu is active

 

 

 

On

Normal

operation.

Configuration

 

 

 

 

 

menu is deactived

 

 

 

 

 

Flashing

Communication with the Environment

 

 

 

 

 

Sensor (option).

 

 

 

3.3Installation in the UPS

The Network Management Card (66123) can be "hot" installed in the MGE Galaxy 7000 UPS or SSC unit.

Note the card's MAC address prior to insertion

Connect the ETHERNET cable

Insert and tighten the card's retaining screws

Wait 3 min.; the card is completely operational when the green UPS Data LED flashes continuously

3.4Sensor installation (option)

The Environment sensor is available as an option on the Network Management Card. SKU number is 66846.

The sensor allows remote monitoring of the UPS's environment through regular measurements: temperature, humidity, status of two external contacts. It also enables notification of alarms (e-mail, trap SNMP) according to pre-programmed thresholds.

It is connected to the Service port (Settings/Sensor) directly on the Network Management Card with a standard Ethernet cable (20 meters maximum).

Recognition is automatic. Supervision and configuration are performed via a menu that can be accessed directly from the home page.