Issue A1 2 Installation
MICROMASTER 410 Operating Instructions
6SE6400-5EA00-0BP0 21
2.4 Harmonic CurrentsHarmonic currents with 1% mains impedance.
Table 2-1 Single Phase 115 V Connection
MLFB Filter Type Power
CT (kW) Fundamen-
tal Amps 3rd
Amps 5th
Amps 7th
Amps 9th
Amps 11th
Amps 13th
Amps
6SE6410-2UA11-2AA0 UNFILTERED 0,12 2,90 2,80 2,60 2,35 2,00 1,68 1,30
6SE6410-2UA12-5AA0 UNFILTERED 0,25 5,65 5,30 4,68 3,80 2,87 1,98 1,27
6SE6410-2UA13-7AA0 UNFILTERED 0,37 7,94 7,32 6,07 4,57 3,05 1,87 1,24
6SE6410-2UA15-5BA0 UNFILTERED 0,55 11,25 10,10 8,06 5,67 3,50 2,00 1,58
Table 2-2 Single Phase 230 V Connection
MLFB Filter Type Power
CT (kW) Fundamen-
tal Amps 3rd
Amps 5th
Amps 7th
Amps 9th
Amps 11th
Amps 13th
Amps
6SE6410-2BB11-2AA0 B
6SE6410-2UB11-2AA0 UNFILTERED 0,12 1,34 1,20 0,83 0,45 0,18 0,12 0,06
6SE6410-2BB12-5AA0 B
6SE6410-2UB12-5AA0 UNFILTERED 0,25 2,90 2,40 1,70 0,95 0,40 0,20 0,20
6SE6410-2BB13-7AA0 B
6SE6410-2UB13-7AA0 UNFILTERED 0,37 4,10 3,50 2,50 1,40 0,60 0,25 0,25
6SE6410-2BB15-5BA0 B
6SE6410-2UB15-5BA0 UNFILTERED 0,55 5,30 4,60 3,30 1,80 0,70 0,40 0,40
6SE6410-2BB17-5BA0 B
6SE6410-2UB17-5BA0 UNFILTERED 0,75 7,30 6,50 4,40 2,50 1,00 0,50 0,50
2.5 Derating with Pulse FrequenciesTable 2-3 Derating with Pulse Frequencies
Measured Output Current (A)
Power
(kW) 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz 14 kHz 16 kHz
0.12 0.9 0.9 0.9 0.8 0.7 0.6 0.5
0.25 1.7 1.7 1.7 1.5 1.3 1.1 0.9
0.37 2.3 2.3 2.3 2.0 1.7 1.5 1.3
0.55 3.2 3.2 3.2 2.9 2.6 2.3 2.0
0.75 3.9 3.9 3.6 3.2 2.9 2.6 2.3
0.75 (40º C) 4.2 4.2 4.2 3.8 3.4 3.0 2.7
All currents are rated at 50 ºC unless otherwise stated