9 Electro-Magnetic Compatibility Issue A1
MICROMASTER 410 Operating Instructions
72 6SE6400-5EA00-0BP0
Case 3: Filtered - for residential, commercial and light industry
This level of performance will allow the manufacturer / assem bler to self-certify
compliance of their apparatus with the EMC directive for the residentia l,
commercial and light industrial environment as regards the EMC perf ormance
characteristics of the power drive system. Performance limits are as specified in
the generic emission and immunity standards EN 50081-1 and EN 50082- 1.
Table 9-3 Case 3 - Filtered for Residential, Commercial and Light Industry
EMC Phenomenon Standard Level
Emissions:
Radiated Emissions* EN 55022 Level B
Conducted Emissions EN 55022 Level B
Immunity:
Supply Voltage Distortion EN 61000-2-4
Voltage Fluctuations, Dips, Unbalance,
Frequency Variations EN 61000-2-1
Magnetic Fields EN 61000-4-8 50 Hz, 30 A/m
Electrostatic Discharge EN 61000-4-2 8 kV air discharge
Burst Interference EN 61000-4-4 2 kV power cables (Level 3),
2 kV control (Level 4)
Radio-frequency Electromagnetic Field,
pulse modulated ENV 50 204 900 MHz, 10 V/m 50% duty cycle,
200 Hz repetition rate
* These limits are dependent on the inverter being correctly installed inside a
metallic switchgear enclosure. The limits will not be met if the in verter is not
enclosed.
NOTICE
To achieve these performance levels, you must not exceed the default P ulse
frequency nor use cables longer than 5 m (16.40 ft).
Table 9-4 Compliance Table
Model Remarks
Case 1 – General Industrial
6SE6410-2U***-**A0 Unfiltered units, all voltages and powers.
Case 2 – Filtered Industrial
6SE6410-2B***-**A0 All units with integral filters for screened motor cables up to 15 m (49.21 ft)
[Class A]
Case 3 – Filtered for residential, commercial and light industry
6SE6410-2B***-**A0 All units with integral filters for screened motor cables up to 5 m (16.40 ft)
[Class B]
* denotes any value is allowed.