3 Commissioning Issue A1
MICROMASTER 410 Operating Instructions
36 6SE6400-5EA00-0BP0
3.2.4.1 Commissioning with the Operator PanelThe Operator Panel (OP) provides access to the inverter
parameters and enables the user to customize the
settings of your MICROMASTER 410. The OP can be
used to configure several MICROMASTER 410 Inverters.
This is accomplished by using the OP to set the required
parameters and once the process is complete, then the
OP can be removed.
The OP contains a five-digit display that allows the user to
read and change parameter values. The OP does not
have the capability to store parameter information.
Table 3-2 shows the factory default settings for operation via the Oper ator Panel.
Notes
♦ The OP motor control functions are disabled by default. To control the m otor
via the OP, parameter P0700 should be set to 1 and P1000 set to 1.
♦ The OP can be fitted to and removed from the inverter whilst power is
applied.
♦ If the OP has been set as the I/O control (P0700 = 1), the drive will stop if the
OP is removed.
Table 3-2 Default settings for operation using the OP
Parameter Meaning Default
P0100 Operating Mode Europe/US 50 Hz, kW
P0307 Power (rated motor) Dimension (kW (Hp)) depending on setting of P0100.
[default value depending on variant.]
P0310 Motor frequency rating 50 Hz (60 Hz) depending on setting of P0100.
P0311 Motor speed rating 1395 (1680) rpm; depending on setting of P0100.
[default value depending on variant]
P1082 Maximum Motor Frequency 50 Hz (60 Hz) depending on setting of P0100.