3 Commissioning Issue A1
MICROMASTER 410 Operating Instructions
34 6SE6400-5EA00-0BP0
3.2.1 Commissioning without an Operator Panel
The inverter is supplied with an LED to indicate the operation state of the unit.
The inverter can be used with its default settings, for a number of app lications. The
default settings are shown in Table 3-1.
The terminal layout is shown in the photograph of the Control Term inal
Connections on the inside of the back cover of this manual.
Table 3-1 Default settings for operation using the standard inverter
Terminals Parameter Default Default Operation
Digital Input 1 1 P0701 = ‘1’ ON/OFF1
Digital Input 2 2 P0702 = ‘12’ Reverse
Digital Input 3 3 P0703 = ‘9’ Fault Acknowledge

Warnings and faults states on the Inverter

The LED indicates the operating status of the inverter. The LED also ind icate
various warnings or fault states. In section 6.1 on page 57 the in verter states,
indicated by the LED are explained.
3.2.2 Basic operation
With the default settings of the inverter the following is possib le:
Ø Start and stopping the motor (DIN1 via external switch)
Ø Reversing the motor (DIN2 via external switch)
Ø Fault Acknowledgement (DIN3 via external switch)
Controlling the speed of the motor is accomplished by connecting the a nalog inputs
as shown in the Figure 3-3 (Switches and potentiometers are not supplied with t he
inverter).
Figure 3-3 Basic operation