2 Installation Issue A1
MICROMASTER 410 Operating Instructions
20 6SE6400-5EA00-0BP0
Shock
Do not drop the inverter or expose to sudden shock. Do not install the inver ter in an
area where it is likely to be exposed to constant vibration.
Mechanical strength to EN 60721-3-3
Ø Deflection: 0.075 mm (10 ... 58 Hz)
Ø Acceleration: 10 m/s2 (58 ... 200 Hz)
Vibration
Do not install the inverter in an area where it is likely to be exposed to c onstant
vibration.
Electromagnetic Radiation
Do not install the inverter near sources of electromagnetic radiation.
Atmospheric Pollution
Do not install the inverter in an environment, which contains atmospheric pollutants
such as dust, corrosive gases, etc.
Water
Take care to site the inverter away from potential water hazards, e.g. do n ot install
the inverter beneath pipes that are subject to condensation. Avoid insta lling the
inverter where excessive humidity and condensation may occ ur.
Installation and cooling
CAUTION
The inverter can be front or side mounted, but MUST be installed in a vertical
position. Mount the inverter vertically to ensure optimum c ooling, see Figure 2-5
on page 23.
Ensure that the inverter’s air vents are not obstructed. Allow 100 mm clearance
above and below the inverter. A clearance of 30 mm on both sides of the inverter is
also required.