Issue A1 3 Commissioning
MICROMASTER 410 Operating Instructions
6SE6400-5EA00-0BP0 37
Buttons on the Operator PanelPanel/Button Function Effects
Indicates
Status The LCD displays the settings currently used by the converter.
Start motor Pressing the button starts the converter. This button is
disabled by default. To enable this button set P0700 = 1.
Stop motor
OFF1 Pressing the button causes the motor to come to a
standstill at the selected ramp down rate. Disabled by
default; to enable set P0700 = 1.
OFF2 Pressing the button twice (or once long) causes the
motor to coast to a standstill.
This function is always enabled.
Change
direction
Press this button to change the direction of rotation of the
motor. Reverse is indicated by a minus (-) sign or a flashing
decimal point. Disabled by default, to enable set P0700 = 1.
Jog motor
Pressing this button while the inverter has no ON command
causes the motor to start and run at the preset jog frequency.
The motor stops when the button is released. Pressing this
button when the motor is running has no effect.
Functions
This button can be used to view additional information.
Pressing and holding the button for 2 seconds from any
parameter during operation, shows the following:
1. DC link voltage (indicated by d – units V).
2. Output frequenc y (Hz)
3. Output voltage (ind ic ate d by o – units V).
4. The value se lected in P0005
Additional presses will toggle around the above displays.
A short press of the button will acknowledge a fault condition.
Jump Function
From any parameter (rXXXX or PXXXX) a short press of the
Fn button will immediately jump to r0000, you can then
change another parameter, if required. Upon returning to
r0000, pressing the Fn button will return you to your starting
point.
Access
parameters Pressing this button allows access to the parameters.
Increase
value Pressing this button increases the displayed value.
Decrease
value Pressing this button decreases the displayed value.
Figure 3-5 Buttons on the Operator Panel