Issue A1 9 Electro-Magnetic Compatibility
MICROMASTER 410 Operating Instructions
6SE6400-5EA00-0BP0 71
9.1.4 General cases of EMC performance
Three General cases of EMC performance are available as detailed be low:

Case 1: General Industrial

Compliance with the EMC Product Standard for Power Drive Systems EN 68100- 3
for use in Second Environment (Industrial) and Restricted Distribution.
Table 9-1 Case 1 - General Industrial
EMC Phenomenon Standard Level
Emissions:
Radiated Emissions EN 55011 Level A1
Conducted Emissions EN 68100-3 Limits under consideration
Immunity:
Electrostatic Discharge EN 61000-4-2 8 kV air discharge
Burst Interference EN 61000-4-4 2 kV power cables (Level 3),
1 kV control (Level 3)
Radio Frequency Electromagnetic Field IEC 1000-4-3 26-1000 MHz, 10 V/m

Case 2: Filtered Industrial

This level of performance will allow the manufacturer/assem bler to self-certify their
apparatus for compliance with the EMC directive for the industrial en vironment as
regards the EMC performance characteristics of the power drive system.
Performance limits are as specified in the Generic Industrial Emissions and
Immunity standards EN 50081-2 and EN 50082-2.
Table 9-2 Case 2 - Filtered Industrial
EMC Phenomenon Standard Level
Emissions:
Radiated Emissions EN 55011 Level A1
Conducted Emissions EN 55011 Level A1
Immunity:
Supply Voltage Distortion EN 61000-2-4
Voltage Fluctuations, Dips, Unbalance,
Frequency Variations EN 61000-2-1
Magnetic Fields EN 61000-4-8 50 Hz, 30 A/m
Electrostatic Discharge EN 61000-4-2 8 kV air discharge
Burst Interference EN 61000-4-4 2 kV power cables (Level 3),
2 kV control (Level 4)
Radio Frequency Electromagnetic
Field, amplitude modulated ENV 50 140 80-1000 MHz, 10 V/m, 80% AM,
power and signal lines
Radio-frequency Electromagnetic Field,
pulse modulated ENV 50 204 900 MHz, 10 V/m 50% duty cycle,
200 Hz repetition rate