5 System Parameters Issue A1
MICROMASTER 410 Operating Instructions
52 6SE6400-5EA00-0BP0
Motor Data (P0004 = 3)ParNr ParText Default Acc DS QC
r0034 CO: Motor temperature (i2t) - 3 - -
P0300 Select motor type 1 3 C Q
P0304 Rated motor voltage 230 1 C Q
P0305 Rated motor current 3.25 1 C Q
P0307 Rated motor power 0.75 1 C Q
P0308 Rated motor cosPhi 0.000 3 C Q
P0309 Rated motor efficiency 0.0 3 C Q
P0310 Rated motor frequency 50.00 1 C Q
P0311 Rated motor speed 0 1 C Q
P0335 Motor cooling 0 3 CT Q
P0340 Calculation of motor parameters 0 3 CT N
P0610 Motor I2t temperature reaction 2 3 CT N
P0611 Motor I2t time constant 100 3 CT N
P0614 Motor I2t overload warning level 100.0 3 CUT N
P0640 Motor overload factor [%] 190.0 3 CUT Q
P1910 Select motor data identification 0 2 CT Q
Commands and Digital I/O (P0004 = 7)ParNr ParText Default Acc DS QC
r0002 Drive state - 3 - -
r0019 CO/BO: BOP control word - 3 - -
r0052 CO/BO: Act. Status word 1 - 2 - -
r0053 CO/BO: Act. Status word 2 - 2 - -
r0054 CO/BO: Act. Control word 1 - 3 - -
r0055 CO/BO: Add. Act. Control word - 3 - -
P0700 Selection of command source 2 1 CT Q
P0701 Function of digital input 1 1 2 CT N
P0702 Function of digital input 2 12 2 CT N
P0703 Function of digital input 3 9 2 CT N
P0704 Function of digital input 4 0 2 CT N
P0719[2] Selection of cmd. & freq. Setp. 0 3 CT N
r0722 CO/BO: Binary input values - 3 - -
P0724 Debounce time for digital inputs 3 3 CT N
P0731 BI: Function of digital output 1 52:3 2 CUT N
r0747 CO/BO: State of digital outputs - 3 - -
P0748 Invert digital outputs 0 3 CUT N
P0810 BI: CDS bit 0 (Local / Remote) 0:0 3 CUT N