3 Commissioning Issue A1
MICROMASTER 410 Operating Instructions
38 6SE6400-5EA00-0BP0
Changing parameters with the Operator Panel
The procedure for changing the value of parameter P0004 is describ ed below.
Modifying the value of an indexed parameter is illustrated using the example of
P2011. Follow exactly the same procedure to alter other parameters that you wish
to set via the OP.
Changing P0004 – parameter filter function
Step Result on display
1Press to access parameters
2Press until P0004 is displayed
3Press to access the parameter value level
4Press or to the required value
5Press to confirm and store the value
6 Only the motor parameters are visible to the user.
Changing P2011 an indexed parameter
Setting USS address
Step Result on display
1Press to access parameters
2Press until P2011 is displayed
3Press to access the parameter value level
4Press to display current set value
5Press or to the required value
6Press to confirm and store the value
7Press until r0000 is displayed
8Press to return the display to the standard
drive display (as defined by the customer)
Figure 3-6 Changing parameters via the OP