3 Commissioning Issue A1

MICROMASTER 410 Operating Instructions
40 6SE6400-5EA00-0BP0
Flow chart Quick Commissioning (Level 1 Only)
1) Motor related parameters – please refer to motor rating plate.
2) Denotes parameters that contain more detailed lists of possible settings for use in specific
applications. Please refer to the Parameter List
P0100 Operation for Europe/N. America
0 Power in kW; f default 50 Hz
1 Power in hp; f default 60 Hz
2 Power in kW; f default 60 Hz
P0305 Rated Motor Current
1)
A
cceptable Range: 0 - 2 x inverter rated current (A)
Nominal motor current (A) from rating plate
P0307 Rated Motor Power
1)
A
cceptable Range: 0 kW – 1.0 kW (0 hp – 1 hp)
Nominal motor power (kW) from rating plate.
If P0100 = 1, values will be in hp
P0310 Rated Motor Frequenc
y
1)
A
cceptable Range: 12 Hz - 650 Hz
Nominal motor frequency (Hz) from rating plate
P0700 Selection of Command Source
2)
(on / off / reverse)
1 Operator Panel (OP)
2 Terminal / Digital Inputs
P1080 Min. Motor Frequenc
y
Sets minimum motor frequency (0-650Hz) at which
the motor will run irrespective of the frequency
setpoint. The value set here is valid for both
clockwise and anti-clockwise rotation.
P1082 Max. Motor Frequenc
y
Sets maximum motor frequency (0-650Hz) at which
the motor will run at irrespective of the frequency
setpoint. The value set here is valid for both
clockwise and anti-clockwise rotation.
P1120 Ramp-Up Time
A
cceptable Range: 0 s - 650 s
Time taken for the motor to accelerate from
standstill up to maximum motor frequency.
P1121 Ramp-Down Time
A
cceptable Range: 0 s - 650 s
Time taken for motor to decelerate from maximum
motor frequency down to standstill.
P3900 End Quick Commissioning
0 End Quick Commissioning without motor
calculation or factory reset.
1 End Quick Commissioning with motor
calculation and factory reset (Recommended)
2 End Quick Commissioning with motor
calculation and with I/O reset.
3 End Quick Commissioning with motor
calculation but without I/O reset.
P0304 Rated Motor Voltage
1)
A
cceptable Range: 10 V - 2000 V
Nominal motor voltage (V) from rating plate
P0311 Rated Motor Speed
1)
A
cceptable Range: 0 - 40000 1/min
Nominal motor speed (rpm) from rating plate
P0010 Start Quick Commissioning
0 Ready to Run
1 Quick Commissioning
30 Factory Setting
Note
P0010 must always be set back to '0' before
operating the motor. However if P3900 = 1 is set
after commissioning this is done automatically.
P1000 Selection of Frequency Setpoint
2)
1 OP frequency control
↑↓
2 Analogue Setpoint