4 Using the MICROMASTER 410 Issue A1
MICROMASTER 410 Operating Instructions
46 6SE6400-5EA00-0BP0
4.2 Command Sources (P0700)NOTICE
The ramp times and ramp-smoothing functions also affect how the motor starts and
stops. For details of these functions, please refer to parameters P1120, P11 21,
P1130 – P1134 in the Parameter List.
Starting the motor
Ø Default: Terminal 1 (DIN 1, high)
Ø Other settings: see P0700 to P0704
Stopping the motor
There are several ways to stop the motor:
Ø Default:
♦ OFF1 Terminal 1 (DIN 1, low)
♦ OFF2 Off button on Operator Panel, pressing the Off button once
long (two seconds) or twice (with default settings)
♦ OFF3 no standard setting
Ø Other settings: see P0700 to P0704
Reversing the motor
Ø Default: Terminal 2 (DIN 2, high)
Ø Other settings: see P0700 to P0704
4.3 OFF and braking Functions4.3.1 OFF1
This command (produced by canceling the ON command) causes the inv erter to
come to a standstill at the selected ramp-down rate.
Parameter to change ramp-down time see P1121
NOTICE
Ø ON and the following OFF1 command must have the same source.
Ø If the ON/OFF1 command is set to more than one digital input, only the last set
digital input is valid e.g. DIN3 is active.
Ø OFF1 can be combined with DC braking or Compound braking.