Advanced Software Functions (continued)
Logging the | First turn on the base power supply. If the module diagnostics detect no | ||||||
Module in the | problems, the status indicator on the front of the module will light. If the | ||||||
Controller I/O | status indicator does not light, blinks (or goes out during operation), the | ||||||
Configuration | module has detected a failure. For information on viewing failed module | ||||||
Memory | status, refer to your SIMATIC 505 TISOFT2 User Manual |
| |||||
| (PPX:TS505±8101±x). To diagnose and correct a module failure, refer to the | ||||||
| section on troubleshooting. |
|
|
|
| ||
| You must also check that the module is configured in the controller memory. | ||||||
| This is important because the module will appear to be functioning | ||||||
| regardless of whether it is communicating with the controller. To view the | ||||||
| controller memory configuration chart listing all slots on the base and the | ||||||
| inputs or outputs associated with each slot, refer to your SIMATIC 505 | ||||||
| TISOFT2 User Manual. An example chart is shown in Figure | ||||||
| module is properly logged in to the controller as a | ||||||
| analog module the configuration is 16X, 16Y, 32WX, and 32WY registers. | ||||||
|
|
|
| ||||
| 505 I/O MODULE DEFINITION FOR CHANNEL . . . | 1 BASE . . | . . . 00 | ||||
|
| I/O | NUMBER OF BIT AND WORD I/O | SPECIAL | |||
| SLOT | ADDRESS | X | Y | WX | WY | FUNCTION |
| 01 . . . . | . . 0001 | . . 16 . . . . | 16 . . . . | 32 . . . . | 32 | . . NO |
| 02 . . . . | . . 0000 | . . 00 . . . . | 00 . . . . | 00 . . . . | 00 | . . NO |
| . |
|
|
|
|
|
|
| . |
|
|
|
|
|
|
| . |
|
|
|
|
|
|
| 15 . . . . | . . 0000 | . . 00 . . . . | 00 . . . . | 00 . . . . | 00 | . . NO |
| 16 . . . . | . . 0000 | . . 00 . . . . | 00 . . . . | 00 . . . . | 00 | . . NO |
|
|
|
|
|
|
|
|
Figure 3-2 SIMATIC 505±2557 I/O Configuration Chart
In this example, the module is inserted in slot 1 in I/O base 0. The first X point is assigned the first I/O address. In this example, the I/O assignments are: X1 . . X16, Y17 . . Y32, WX33 . . WX64, WY65 . . WY96. For your particular module, look in the chart for the number corresponding to the slot occupied by the module. If word memory and discrete locations appear on this line, then the module is registered in the controller memory and the module is ready for operation.
If the line is blank or erroneous,
Advanced Function Programming | SIMATIC 505±2557 Installation and Operation Guide |