Advanced Software Functions (continued)

Logging the

First turn on the base power supply. If the module diagnostics detect no

Module in the

problems, the status indicator on the front of the module will light. If the

Controller I/O

status indicator does not light, blinks (or goes out during operation), the

Configuration

module has detected a failure. For information on viewing failed module

Memory

status, refer to your SIMATIC 505 TISOFT2 User Manual

 

 

(PPX:TS505±8101±x). To diagnose and correct a module failure, refer to the

 

section on troubleshooting.

 

 

 

 

 

You must also check that the module is configured in the controller memory.

 

This is important because the module will appear to be functioning

 

regardless of whether it is communicating with the controller. To view the

 

controller memory configuration chart listing all slots on the base and the

 

inputs or outputs associated with each slot, refer to your SIMATIC 505

 

TISOFT2 User Manual. An example chart is shown in Figure 3-2. When the

 

module is properly logged in to the controller as a high-density discrete and

 

analog module the configuration is 16X, 16Y, 32WX, and 32WY registers.

 

 

 

 

 

505 I/O MODULE DEFINITION FOR CHANNEL . . .

1 BASE . .

. . . 00

 

 

I/O

NUMBER OF BIT AND WORD I/O

SPECIAL

 

SLOT

ADDRESS

X

Y

WX

WY

FUNCTION

 

01 . . . .

. . 0001

. . 16 . . . .

16 . . . .

32 . . . .

32

. . NO

 

02 . . . .

. . 0000

. . 00 . . . .

00 . . . .

00 . . . .

00

. . NO

 

.

 

 

 

 

 

 

 

.

 

 

 

 

 

 

 

.

 

 

 

 

 

 

 

15 . . . .

. . 0000

. . 00 . . . .

00 . . . .

00 . . . .

00

. . NO

 

16 . . . .

. . 0000

. . 00 . . . .

00 . . . .

00 . . . .

00

. . NO

 

 

 

 

 

 

 

 

Figure 3-2 SIMATIC 505±2557 I/O Configuration Chart

In this example, the module is inserted in slot 1 in I/O base 0. The first X point is assigned the first I/O address. In this example, the I/O assignments are: X1 . . X16, Y17 . . Y32, WX33 . . WX64, WY65 . . WY96. For your particular module, look in the chart for the number corresponding to the slot occupied by the module. If word memory and discrete locations appear on this line, then the module is registered in the controller memory and the module is ready for operation.

If the line is blank or erroneous, re-check the module to ensure that it is firmly seated in the slots. Generate the controller memory configuration chart again. If the line is still incorrect, contact your local distributor or Siemens Energy & Automation, Inc., Technical Services Group.

3-4

Advanced Function Programming

SIMATIC 505±2557 Installation and Operation Guide

Page 34
Image 34
Siemens 505-2557 installation and operation guide Logging, Controller I/O, Memory