Table B-1 Specifications (continued)

Accuracy

10W Cu

(0.5_C at 25_C) (1_C from 0_ to 60_C)

 

100W Pt

(1_F at 25_C) (2_F from 0_ to 60_C)

 

 

(0.5_C at 25_C) (1_C from 0_ to 60_C)

 

120W Ni

(1_F at 25_C) (2_F from 0_ to 60_C)

 

 

(0.5_C at 25_C) (1_C from 0_ to 60_C)

 

 

(1_F at 25_C) (2_F from 0_ to 60_C)

 

 

 

Common Mode Rejection

>130 db @ 60 Hz

 

 

 

 

Normal Mode Rejection

>180 db @ 60Hz

 

 

 

Connector

64 position fixed, wire press in

 

 

 

 

Wire Gauge

18 to 30 AWG

 

 

 

 

 

 

Module Size

Single wide

 

 

 

 

 

 

Backplane Power Consumption

5 Watts

 

 

 

 

Standard Shipping Configuration

3 wire 100 Ohm Pt RTD

 

Digital filtering enabled

 

Degrees Centigrade

 

 

Standard mode 16 WX

 

Scale disabled

 

 

 

 

Isolation

1500 VDC channel group to channel group

 

1500 VDC channel to backplane

 

 

 

Operating Temperature

0_ to 60_C to (32_

to 140_F)

 

 

 

Storage Temperature

±40_ to 85_C (±40_

to 185_F)

 

 

Humidity

0% to 95%, noncondensing

 

 

 

Agency Approvals

UL, UL for Canada

 

 

FM (Class I, Div 2) CE

 

 

 

Shipping Weight

1.5 lbs. (0.68 kg)

 

 

 

 

 

Specifications subject to change without notice

B-2

Specifications

SIMATIC 505±2557 Installation and Operation Guide

Page 64
Image 64