Specifications
B-2 SIMATIC 505–2557 Installation and Operation Guide
Table
B-1
Specifications (continued)
Accuracy 10W
Cu
(0.5_
C at 25
_C) (1_
C from 0
_
to 60
_C)
100W
Pt
(1_
F at 25
_C) (2_
F from 0
_
to 60
_C)
(0.5_
C at 25
_C) (1_
C from 0
_
to 60
_C)
120W
Ni
(1_
F at 25
_C) (2_
F from 0
_
to 60
_C)
(0.5_
C at 25
_C) (1_
C from 0
_
to 60
_C)
(1_
F at 25
_C) (2_
F from 0
_
to 60
_C)
Common Mode Rejection
>130 db @ 60 Hz
Normal Mode Rejection
>180 db @ 60Hz
Connector
64 position fixed, wire press in
W
ire Gauge
18 to 30 A
WG
Module Size Single wide
Backplane Power Consumption
5 W
atts
Standard Shipping Configuration
3 wire 100 Ohm Pt RTD
Digital filtering enabled
Degrees Centigrade
Standard mode 16 WX
Scale disabled
Isolation
1500 VDC channel group to channel group
1500 VDC channel to backplane
Operating T
emperature 0_
to 60
_
C to (32
_to
140
_F)
Storage T
emperature –40_
to 85
_
C (–40
_to
185
_F)
Humidity
0% to 95%, noncondensing
Agency Approvals
UL, UL for Canada
FM (Class
I
, Div 2) CE
Shipping W
eight
1.5 lbs. (0.68 kg)
Specifications subject to change without notice