2.2Wiring the Input Connectors

RTD input signals are accepted through a 64 position fixed connector with wire press in terminals located on the front of the module. Consult the RTD manufacturer's recommendations for selecting the input wire type and size. The connector will accept 18 to 30 AWG wire.

The SIMATIC 505±2557 uses a fixed connector to terminate field wiring. This is used because the chemistry of a removable connector may have an adverse effect on the accuracy of the measurement. Siemens has carefully selected a connector that minimizes this effect.

Refer to Figure 2-5 for correct wiring for 2, 3, or 4 wire RTDs to the SIMATIC 505±2557. Each channel consists of four press in terminals. Insert wire by using a small screw driver to depress the spring tension lever and then insert the wire. Solid core wires may be pushed in without depressing lever.

Remove wire by depressing spring lever to remove tension and then remove lead wire. (See Figure 2-4)

The SIMATIC 505±2557 may compensate for up to 20 Ohm of lead resistance per wire. Use the table in Figure 2-1 in planning the maximum distance the RTD may be located from the module.

Figure 2-3 Copper Wire Table at 25 Degrees Celsius

2-8

Installation

SIMATIC 505±2557 Installation and Operation Guide

Page 25
Image 25
Siemens 505-2557 installation and operation guide Wiring the Input Connectors, Copper Wire Table at 25 Degrees Celsius