3.4Timing Considerations
| Without any of the advanced features enabled, the SIMATIC 505±2557 |
| module will update all 16 points in less than 6 msec. With all functions |
| enabled for all 16 points, the module will update all 16 channels in less than |
| 56 msec. Each function has a specific overhead associated with it and your |
| application should consider the time delays to ensure that there is adequate |
| time allowed for the processing of data. |
Timing Constraints | Table |
When Using | each of the advanced functions is enabled. Operations such as scaling and |
Advanced | offset mode require the greatest amount of time due to the multiplication |
Functions | and division in the microcomputer. |
| Table |
Functions Enabled in Enhanced Mode (32 WX and 32 WY, 16 X and 16 Y)
Time for All 16 Channels
|
|
None | 6.5 msec |
|
|
Low alarm | 7.73 msec |
|
|
High alarm | 7.73 msec |
|
|
Scaling | 27.1 msec |
|
|
Offset mode | 27.1 msec |
|
|
Filtering | 8.97 msec |
|
|
Averaging | 7.85 msec |
|
|
Averaging reset (16 channels) | 41.8 msec |
|
|
Peak hold | 7.65 msec |
|
|
Valley hold | 7.65 msec |
|
|
|
|
16 WX MODE |
|
|
|
|
|
No digital filtering | 5.80 msec |
|
|
Filtering enabled | 8.20 msec |
|
|
SIMATIC 505±2557 Installation and Operation Guide |